Representation Of Analog Values In Voltage Measuring Ranges - Siemens SIMATIC ET 200SP Manual

Analog input module ai 8xu ba 6es7134-6ff00-0aa1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

B.2

Representation of analog values in voltage measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible voltage
measuring ranges.
Table B- 4
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Table B- 5
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
Analog input module AI 8xU BA (6ES7134-6FF00-0AA1)
Manual, 03/2015, A5E34941660-AA
B.2 Representation of analog values in voltage measuring ranges
Voltage measuring range ±10 V
Voltage measuring range
Hex.
±10 V
7FFF
>11.759 V
7EFF
11.759 V
6C01
6C00
10 V
5100
7.5 V
1
361.7 µV
0
0 V
FFFF
AF00
-7.5 V
9400
-10 V
93FF
8100
-11.759 V
8000
<-11.759 V
Voltage measuring range 0 to 10 V
Voltage measuring range
Hex.
0 to 10 V
7FFF
>11.759 V
7EFF
11.759 V
6C01
6C00
10 V
5100
7.5 V
1
0 V + 361.7 µV
0
0 V
FFFF
ED00
-1.759 V
8000
< -1.759 V
Representation of analog values
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
31