Representation of analog values
B.3 Representation of analog values in voltage measuring ranges
B.3

Representation of analog values in voltage measuring ranges

Voltage measuring range ±10 V to ±5 V
Table B- 4
System
dec
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Voltage measuring ranges 1 V to 5 V and 0 V to 10 V
Table B- 5
System
dec
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
34
Voltage measuring range ±10 V to ±5 V
Voltage measuring range
hex
±10 V
7FFF
>11.759 V
7EFF
11.759 V
6C01
6C00
10 V
5100
7.5 V
1
361.7 µV
0
0 V
FFFF
AF00
-7.5 V
9400
-10 V
93FF
8100
-11.759 V
8000
<-11.759 V
Voltage measuring ranges 1 V to 5 V and 0 V to 10 V
Voltage measuring range
hex
1 V to 5 V
7FFF
>5.704 V
7EFF
5.704 V
6C01
6C00
5 V
5100
4 V
1
1 V + 144.7 µV
0
1 V
FFFF
ED00
0.296 V
8000
<0.296 V
±5 V
>5.879 V
5.879 V
5 V
3.75 V
180.8 µV
0 V
-3.75 V
-5 V
-5.879 V
<-5.879 V
0 V to 10 V
>11.759 V
11.759 V
10 V
7.5 V
0 V + 361.7 µV
0 V
-1.759 V
<-1.759 V
Analog input module AI 2xU ST (6ES7134-6FB00-0BA1)
Manual, 12/2015, A5E36104728-AA
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Range
Overflow
Overrange
Nominal range
Underrange
Underflow