Representation Of Analog Values In Voltage Measuring Ranges - Siemens ET 200SP Manual

Analog input module, ai 4xu/i 2-wire st 6es7134-6hd01-0ba1
Hide thumbs Also See for ET 200SP:
Table of Contents

Advertisement

B.2

Representation of analog values in voltage measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible voltage
measuring ranges.
Table B- 4
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Table B- 5
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
* negative values are only possible if the module (6ES7134-6GD01-0BA1) with FW version V2.0.0 and
higher is configured.
** no underrange/underflow if the predecessor module (6ES7134-6GD00-0BA1) is configured.
Analog Input Module AI 4xU/I 2-wire ST (6ES7134-6HD01-0BA1)
Manual, 12/2017, A5E03572832-AD
B.2 Representation of analog values in voltage measuring ranges
Voltage measuring range ±10 V and ±5 V
Voltage measuring range
Hex.
±10 V
7FFF
>11.759 V
7EFF
11.759 V
6C01
6C00
10 V
5100
7.5 V
1
361.7 µV
0
0 V
FFFF
AF00
-7.5 V
9400
-10 V
93FF
8100
-11.759 V
8000
<-11.759 V
Voltage measuring range 1 to 5 V and 0 to 10 V
Voltage measuring range
Hex.
1 to 5 V
7FFF
>5.704 V
7EFF
5.704 V
6C01
6C00
5 V
5100
4 V
1
1 V + 144.7 µV
0
1 V
FFFF
ED00
0.296 V
8000
<0.296 V
Representation of analog values
±5 V
>5.879 V
5.879 V
5 V
3.75 V
180.8 µV
0 V
-3.75 V
-5 V
-5.879 V
<-5.879 V
Range
0 to 10 V
>11.759 V
Overflow
11.759 V
Overrange
10 V
Nominal range
7.5 V
0 V + 361.7 µV
0 V
Underrange **
-1.759 V *
<-1.759 V *
Underflow **
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents