Parameters - Siemens SIMATIC ET 200SP Manual

Analog input module ai 8xu ba 6es7134-6ff00-0aa1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

4.2

Parameters

AI 8xU BA parameters
The effective range of the configurable parameters depends on the type of configuration.
The following configurations are possible:
● Central operation with an ET 200SP CPU
● Distributed operation on PROFINET IO in an ET 200SP system
● Distributed operation on PROFIBUS DP in an ET 200SP system
When assigning the parameters in the user program, the "WRREC" instruction transfers the
parameters to the module using data records, see section Parameter assignment and
structure of the parameter data record (Page 25)).
The following parameter settings are possible:
Table 4- 2
Configurable parameters and their defaults (GSD file)
Parameter
Diagnostics:
No supply voltage L+
Diagnostics:
Overflow
Diagnostics:
Underflow
Type/range of meas-
urement
Smoothing
Analog input module AI 8xU BA (6ES7134-6FF00-0AA1)
Manual, 03/2015, A5E34941660-AA
Range of values
Disable
Enable
Disable
Enable
Disable
Enable
Deactivated
Voltage +/- 10 V
Voltage 0 to 10 V
None
Weak
Medium
Strong
Default
Reconfigura-
tion in RUN
Disable
Yes
Disable
Yes
Disable
Yes
Voltage (+/- 10
Yes
V)
None
Yes
Parameters/address space
4.2 Parameters
Effective range with configura-
tion software, e.g. STEP 7
(TIA Portal)
GSD file
GSD file
PROFINET
PROFIBUS DP
IO
Module
Module
Module
Module
1
Module
Channel
Channel
Channel
Channel
13