Parameter assignment and structure of the parameter data record

Parameter assignment in the user program
The module can be re-configured in RUN (for example, the voltage or current values of
selected channels can be changed in RUN without having an effect on the other channels).
Changing parameters in RUN
The "WRREC" instruction is used to transfer the parameters to the module using data
record 128. The parameters set in STEP 7 are not changed in the CPU, which means the
parameters set in STEP 7 are valid again after a restart.
STATUS output parameter
If errors occur when transferring parameters with the "WRREC" instruction, the module
continues operation with the previous parameter assignment. The STATUS output
parameter contains a corresponding error code.
You will find a description of the "WRREC" instruction and the error codes in the STEP 7
online help.
Analog input module AI 8xU BA (6ES7134-6FF00-0AA1)
Manual, 03/2015, A5E34941660-AA
A.2 Parameter assignment and structure of the parameter data record
Parameter data record
25