B.2

Representation of analog values in voltage measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible voltage
measuring ranges.
Table B- 4
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Table B- 5
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
Analog input module AI 2xU/I 2-/4-wire HS (6ES7134-6HB00-0DA1)
Manual, 09/2018, A5E03576060-AF
B.2 Representation of analog values in voltage measuring ranges
Voltage measuring range ±10 V and ±5 V
Voltage measuring range
Hex.
±10 V
7FFF
> 11.759 V
7EFF
11.759 V
6C01
6C00
10 V
5100
7.5 V
1
361.7 µV
0
0 V
FFFF
AF00
-7.5 V
9400
-10 V
93FF
8100
-11.759 V
8000
< -11.759 V
Voltage measuring range 1 V to 5 V and 0 V to 10 V
Voltage measuring range
Hex.
1 to 5 V
7FFF
> 5.704 V
7EFF
5.704 V
6C01
6C00
5 V
5100
4 V
1
1 V + 144.7 µV
0
1 V
FFFF
ED00
0.296 V
8000
< 0.296 V
Representation of analog values
±5 V
> 5.879 V
5.879 V
5 V
3.75 V
180.8 µV
0 V
-3.75 V
-5 V
-5.879 V
< -5.879 V
0 to 10 V
> 11.759 V
11.759 V
10 V
7.5 V
361.7 µV
0 V
-1.759 V
< -1.759 V
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
47