Grounding The Device - Emerson FB1200 Instruction Manual

Flow computer
Hide thumbs Also See for FB1200:
Table of Contents

Advertisement

2.8

Grounding the Device

The flow computer includes a grounding lug on the terminal plate.
Figure 2-18: Ground Lug
1
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
Once you have installed the unit, run a ground wire between the ground lug and a known good
earth ground. You route the ground wire through one of the conduit fittings.
Use stranded copper wire to earth ground, and keep the length as short as possible.
Clamp or braze the ground wire to the ground bed conductor (typically a stranded copper
AWG 0000 cable installed vertically or horizontally).
Using a high-wattage soldering iron, tin the wire ends with solder before you insert them into
the chassis ground lug.
Run the ground wire so that any routing bend in the cable has a minimum radius of 30.5 cm
(12 inches) below ground and 20.4 cm (8 inches) above ground.
For more information on grounding or if your installation uses cathodic protection, refer to Site
Considerations for Equipment Installation, Grounding, and Wiring (D301452X012).
Installation
Ground Lug
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2017
25