Chapter 3 Electrical Installation
Port
J5.2
J5.3
J5.4

3.2.6 Remote EPO Input Port

he UPS has the EPO function that operates by a switch on the operator control and display panel of the UPS or
T
by a remote contact provided by the user. The EPO switch is under a hinged, plastic shield.
J10 is the remote EPO input port. The port is shown in Figure 3-12 and described in Table 3-7.
EPO is triggered when pins 3 and 4 of J10 are shorted or pins 2 and 1 of J10 are opened.
If an external EPO facility is required, pins 1 and 2 or 3 and 4 of J10 are reserved for this function. The external
EPO facility is also connected to the normally open or normally closed remote stop switch between these two
terminals using shielded cable. If this function is not used, pins 3 and 4 of J10 must be opened or pins 1 and 2
of J10 must be shorted.
1. The UPS EPO action shuts down the rectifiers, inverters and static bypass. But it does not internally disconnect the
input power supply. To disconnect all power to the UPS, open the upstream input switch when EPO is activated.
2. Pins 1 and 2 of J10 are supplied factory-shorted.

3.2.7 RS485 Port, RS232 Port And Intellislot Port

The RS485 and RS232 ports provide serial data and are intended for use by authorized commissioning and
service personnel in UPS commissioning and service.
The three Intellislot ports are used to install optional communication cards at site, including relay card,
Modbus card, SIC card and UF-RS485 card. For details, refer to Chapter 8 Option.
Table 3-6 Description of output dry contact port
Name
BFP_O
Bypass feedback protection relay (normally open), closed when bypass SCR is shorted
BFP_S
Bypass feedback protection relay center
BFP_C
Bypass feedback protection relay (normally closed), open when bypass SCR is shorted
Figure 3-12 Remote EPO input port
Table 3-7 Description of remote EPO input port
Port
J10.1
J10.2
J10.3
J10.4
Liebert APM 90 Integrated Modular UPS User Manual
Description
+12V
J10
Name
EPO_NC
+12V
+12V
EPO_NO
Note
Description
EPO activated when shorted to J10.2
EPO activated when shorted to J10.1
EPO activated when opened to J10.4
EPO activated when opened to J10.3