Field Settings; Outdoor Unit; Setting Mode 1 (H1P Off); Setting Mode 2 (H1P On) - Daikin RMXS-L Series Service Manual

Multi-split type air conditioners
Hide thumbs Also See for RMXS-L Series:
Table of Contents

Advertisement

SiUS181631EA

2. Field Settings

2.1

Outdoor Unit

2.1.1 Setting Mode and Monitor Mode
Outline
The following 3 modes can be changed over with the button switches on the service PCB and you
can find the present mode by the status of the H1P indicator.

(1) Setting mode 1 (H1P off)

Initial status (normal) : Also indicates during abnormal.

(2) Setting mode 2 (H1P on)

Used to modify the operating status and to set program addresses, etc. Usually used in servicing
the system.
(3) Monitor mode (H1P blinks)
Used to check the program made in setting mode 2.
Press BS1 (MODE button) for more than
5 seconds.
Setting mode 2
Select a setting item with
BS2 (SET button).
Press BS3 (RETURN button).
Select a setting condition
with BS2 (SET button).
Press BS3 (RETURN button).
Setting condition
(Contents) display
Press BS3 (RETURN button).
Test Operation and Field Settings
BS1
(MODE)
Setting mode 1
(Initial condition)
H1P
MODE
H1P
ON
MODE
Press BS1 (MODE button).
H1P H3P H5P H7P
H2P H4P H6P
BS2
BS3
BS4
(SET)
(RETURN)
(TEST)
(RESET)
(R15629)
Press BS1 (MODE button).
OFF
Monitor mode
Select a check item with
BS2 (SET button).
Press BS3 (RETURN button).
Contents display
Press BS3 (RETURN button).
Field Settings
BS5
H1P
Blinking
MODE
Press BS1 (MODE button).
(R23983)
125