Program Dry Operation - Daikin RMXS-L Series Service Manual

Multi-split type air conditioners
Hide thumbs Also See for RMXS-L Series:
Table of Contents

Advertisement

CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions
COMFORT
CTXG, CTXS-L, FTXS-L Series
AIRFLOW
Operation
7.4

Program Dry Operation

Outline
Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and FAN setting buttons are inoperable.
Details
The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two zones.
Then, the unit operates in an appropriate capacity for each zone to maintain the temperature and
humidity at a comfortable level.
temperature at start-up
78
The fan speed is automatically controlled within the following steps.
Cooling
L tap ~ MH tap (same as AUTOMATIC)
Heating
In order to obtain a comfortable airflow, the fan speed may be set to a rate different from
automatic fan speed control.
The latest command has the priority between POWERFUL and COMFORT AIRFLOW.
Room temperature
X – 1.0°C (1.8°F)
Y = X – 2.5°C (4.5°F)
or
Y = X – 2.0°C (3.6°F)
Room thermistor
Target temperature
24°C or more
(75.2°F or more)
temperature at start-up
18 ~ 23.5°C
(64.4 ~ 74.3°F)
17.5°C or less
(63.5°F or less)
Thermostat turns on also when the room temperature is in the zone B for 10 minutes.
Zone C = Thermostat ON
Zone B
Zone A = Thermostat OFF
Thermostat OFF point
X
Room thermistor
18°C
(64.4°F)
Room temperature
Target temperature X
Z = X – 0.5°C (0.9°F)
Thermostat ON point
Y
X – 2.5°C
X – 0.5°C
(X – 4.5°F)
(X – 0.9°F)
X – 2.0°C
X – 0.5°C
(X – 3.6°F)
(X – 0.9°F)
X – 2.0°C
X – 0.5°C = 17.5°C
(X – 3.6°F)
(X – 0.9°F = 63.5°F)
Functions and Control
SiUS181631EA
(R24029)
Z ★