Indoor Fan Motor Or Related Abnormality - Daikin RMXS-L Series Service Manual

Multi-split type air conditioners
Hide thumbs Also See for RMXS-L Series:
Table of Contents

Advertisement

SiUS181631EA
4.3

Indoor Fan Motor or Related Abnormality

4.3.1 Indoor Fan Motor (DC Motor) or Related Abnormality
Applicable
CTXG09/12/18QVJUW(S)
CTXS07JVJU
Models
CTXS09/12HVJU
CTXS07LVJU
FTXS09/12/15/18/24LVJU
FVXS09/12/15/18NVJU
A6
Error Code
Method of Error
The rotation speed detected by the Hall IC during indoor fan motor operation is used to determine
abnormal fan motor operation.
Detection
Error Decision
The detected rotation speed does not reach the demanded rotation speed of the target tap, and is
less than 50% of the maximum fan motor rotation speed.
Conditions
Supposed
Causes
Troubleshooting
Remarkable decrease in power supply voltage
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective capacitor of the fan motor
Defective indoor unit PCB
Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series