12. Field settings and test run

(1 )Check if the electrical component box covers of the indoor
unit and outdoor unit are fastened securely.
(2)Field settings.
<According to the installation condition, make the field
settings using the remote controller after turning on the
power supply. Please perform in accordance with
"Field settings" of the manual included with the remote
controller.
>
• Make the settings by changing the "mode number",
"1 st coded number'' and "2nd coded number''.
• For setting procedure and operating method, refer to
the "Field settings" of the manual included with the
remote controller.
Values marked with
setting the indoor unit separately during group control.
• During remote control, perform input changeover of
"Forced OFF" and "ON/OFF" with the remote
controller. After start the field settings, select the
mode number "12" and set the 1st coded number and
the 2nd coded number to "1" and "01" respectively.
This is "Forced OFF"
• Set the 2nd coded number to "02" for "ON/OFF"
operation. (Factory setting is "Forced OFF").
After finishing field settings, deliver the "Field settings"
and operation manual to the customers for keeping
and future reference.
a .
Settings when installing the optional accessories
• For settings when installing the optional accessories,
refer to the installation manual included with the
optional accessories.
b.
Setting the air filter cleaning signal
• The remote controller is equipped with the aid filter
cleaning signal LCD, to display the time to clean the air
filter.
• Refer to the table below and change the 2nd coded
number in accordance with the room conditions.
(Factory setting of the 2nd coded number is "01" and it
means mild filter contamination.)
Air filter
Setting
cleaning signal
display
Air filter contami-
About 2500
nation-light
hours
Air filter contami-
About 1250
nation-heavy
hours
*
and () are the ones when
1st
Mode
coded
coded
number
number
number
10(20)
0
Perform test run based on the operation & installation
manual of the outdoor unit
• If something unusual occurs, the operation lamp of the
remote controller will flash.
Check the malfunction code displayed on the LCD to
determine the position of the fault.
For malfunction codes and correspondent
explanations, refer to the "Service precautions" of the
indoor unit.
If the following signals are indicated on the display,
then the wiring may be improper or the power supply is
not turned on. In this case, check again.
Display
Displaying "Under
centralized control
�"
Displaying "t:3"
Displaying " U'-1 "
Displaying " UH "
No display
If the test run is performed while the room is under
construction; do not operate the unit until construction is
complete.
Operating the unit in such conditions may result in damage
to the unit and surroundings.
2nd
01
02
Description
• Shot circuit of the forced-OFF terminals
{T1, T2).
• Test run has not been completed.
• The outdoor unit is not powered up.
• The outdoor unit is not connected to the
power wiring.
• The transmission wiring and the forced-
OFF terminals (T1, T2) are incorrectly
connected.
• The transmission wiring is disconnected.
• The indoor unit is not powered up.
• The indoor unit is not connected to the
power wiring.
• The remote controller connecting &
transmission wiring terminals (F1, F2)
and forced-OFF terminals (T1, T2) are
incorrectly connected.
• The remote controller transmission
wiring is disconnected.