7.3.3
Example: Automatic mode during cooling
A
B
T
e
C
D
6°C
3°C
A
Actual load curve
B
Virtual load curve (initial capacity automatic mode)
C
Virtual target value (initial evaporation temperature value
automatic mode)
D
Required evaporation temperature value
E
Load factor
F
Outside air temperature
T
Evaporating temperature
e
Quick
Powerful
Mild
Room temperature evolution:
D
E
F
A
B
A
Indoor unit set temperature
B
Operation start
C
Operating time
D
Mild
E
Quick
F
Powerful
RYYQ+RYMQ+RXYQ8~20T7Y1B
VRV IV system air conditioner
4P370475-1C – 2016.11
7.3.4
E
100%
50%
49°C
46°C
35°C
F
Room temperature evolution:
A
C
Example: Automatic mode during heating
T
c
C
D
2°C
A
Virtual load curve (default automatic mode peak capacity)
B
Load curve
C
Virtual target value (initial condensation temperature value
automatic mode)
D
Design temperature
E
Load factor
F
Outside air temperature
T
Condensing temperature
c
Quick
Powerful
Mild
F
E
D
B
A
Indoor unit set temperature
B
Operation start
C
Operating time
D
Mild
E
Quick
F
Powerful
7 Configuration
E
100%
A
B
70%
F
C
Installer and user reference guide
47