Error codes when charging refrigerant

Code
Cause
Unusual low pressure on
suction line
Freeze-up prevention
indoor unit
Indoor unit is out of
temperature range for leak
detection operation
Outdoor unit is out of
temperature range for leak
detection operation
Indicates an indoor unit
which is not compatible
with leak detection
functionality is installed
(e.g., RA DX indoor unit,
Hydrobox, ...)
Other
malfunction
code
6.7.9

Checks after charging refrigerant

▪ Are all stop valves open?
▪ Is the amount of refrigerant, that has been added, recorded on the
refrigerant charge label?
NOTICE
Make sure to open all stop valves after (pre-) charging the
refrigerant.
Operating with the stop valves closed will damage the
compressor.
6.7.10
To fix the fluorinated greenhouse gases
label
1 Fill in the label as follows:
Contains fluorinated greenhouse gases
RXXX
1
=
f
GWP: XXX
2
=
2
1
+
1
2
=
GWP × kg
=
1000
RYYQ+RYMQ+RXYQ8~20T7Y1B
VRV IV system air conditioner
4P370475-1C – 2016.11
Solution
Close valve A
immediately. Push BS3 to
reset. Check following
items before retrying
autocharge procedure:
▪ Check if the gas side
stop valve is opened
correctly.
▪ Check if the valve of the
refrigerant cylinder is
opened.
▪ Check if the air inlet and
outlet of the indoor unit
are not obstructed.
Close valve A
immediately. Push BS3 to
reset. Retry autocharge
procedure.
Retry when ambient
conditions are satisfied.
Retry when ambient
conditions are satisfied.
Refer to requirements to
be able to execute leak
detection operation.
Close valve A
immediately. Confirm the
malfunction code and take
corresponding action,
"10.2 Solving problems
based on error codes" on
page 52.
a
kg
b
kg
c
d
kg
e
tCO
eq
2
a
If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e
Greenhouse gas emissions of the total refrigerant charge
expressed as tonnes CO
f
GWP = Global warming potential
NOTICE
In Europe, the greenhouse gas emissions of the total
refrigerant charge in the system (expressed as tonnes
CO
-equivalent) is used to determine the maintenance
2
intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
2 Fix the label on the inside of the outdoor unit near the gas and
liquid stop valves.
6.8

Connecting the electrical wiring

6.8.1
Precautions when connecting electrical
wiring
DANGER: RISK OF ELECTROCUTION
WARNING
All field wiring and components must be installed by a
licensed electrician and must comply with the applicable
legislation.
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category  III
condition, shall be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
Install power cables at least 1 metre away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
1 metre may not be sufficient.