Preparing Electrical Wiring; About Electrical Compliance; Safety Device Requirements - Daikin RYYQ8T7Y1B Installer And User Reference Manual

Vrv iv system
Table of Contents

Advertisement

5 Preparation
▪ If the piping length between the outdoor units exceeds 2 m, create
a rise of 200  mm or more in the gas line within a length of 2  m
from the kit.
If
≤2 m
a
>2 m
a
≤2 m
a
To indoor unit
b
Piping between outdoor units
NOTICE
There are restrictions on the refrigerant pipe connection
order between outdoor units during installation in case of a
multiple outdoor unit system. Install according to following
restrictions. The capacities of outdoor units A, B and C
must fulfill the following restriction conditions: A≥B≥C.
A
B
a b
c
a To indoor units
b Outdoor unit multi connecting piping kit (first branch)
c Outdoor unit multi connecting piping kit (second branch)
5.4

Preparing electrical wiring

5.4.1

About electrical compliance

This equipment complies with:
▪ EN/IEC 61000‑3‑11 provided that the system impedance Z
less than or equal to Z
at the interface point between the user's
max
supply and the public system.
▪ EN/IEC
61000‑3‑11
=
Standard setting the limits for voltage changes, voltage
fluctuations and flicker in public low-voltage supply systems for
equipment with rated current ≤75 A.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a system impedance Z
▪ EN/IEC 61000‑3‑12 provided that the short-circuit power S
greater than or equal to the minimum S
point between the user's supply and the public system.
▪ EN/IEC
61000‑3‑12
=
Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current >16 A and ≤75 A per phase.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a short-circuit power S
minimum S
value.
sc
Installer and user reference guide
20
Then
b
≤2 m
>2 m
>2 m
b
≤2 m
C
European/International
Technical
less than or equal to Z
.
sys
max
value at the interface
sc
European/International
Technical
greater than or equal to the
sc
Model
RYYQ8/RYMQ8/RXYQ8
RYYQ10/RYMQ10/RXYQ10
RYYQ12/RYMQ12/RXYQ12
RYYQ14/RYMQ14/RXYQ14
RYYQ16/RYMQ16/RXYQ16
RYYQ18/RYMQ18/RXYQ18
RYYQ20/RYMQ20/RXYQ20
RYYQ22/RXYQ22
RYYQ24/RXYQ24
RYYQ26/RXYQ26
RYYQ28/RXYQ28
RYYQ30/RXYQ30
RYYQ32/RXYQ32
RYYQ34/RXYQ34
RYYQ36/RXYQ36
RYYQ38/RXYQ38
RYYQ40/RXYQ40
RYYQ42/RXYQ42
RYYQ44/RXYQ44
RYYQ46/RXYQ46
RYYQ48/RXYQ48
RYYQ50/RXYQ50
RYYQ52/RXYQ52
RYYQ54/RXYQ54
INFORMATION
Multi units are standard combinations.
5.4.2

Safety device requirements

The power supply must be protected with the required safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage protector in accordance with the applicable legislation.
For standard combinations
Selection and sizing of the wiring should be done in accordance with
the applicable legislation based on the information mentioned in the
is
sys
table below.
INFORMATION
Multi units are standard combinations.
Model
RYYQ8/RYMQ8/RXYQ8
RYYQ10/RYMQ10/RXYQ10
RYYQ12/RYMQ12/RXYQ12
is
RYYQ14/RYMQ14/RXYQ14
sc
RYYQ16/RYMQ16/RXYQ16
RYYQ18/RYMQ18/RXYQ18
RYYQ20/RYMQ20/RXYQ20
RYYQ22/RXYQ22
RYYQ24/RXYQ24
RYYQ26/RXYQ26
RYYQ28/RXYQ28
RYYQ30/RXYQ30
RYYQ32/RXYQ32
Z
(Ω)
Minimum S
max
sc
value (kVA)
1216
564
615
917
924
873
970
1179
2140
1532
1539
1488
1848
1797
1894
2750
2052
2412
2463
2765
2772
2721
2670
2619
Minimum
Recommended
circuit
fuses
ampacity
16.1 A
20 A
22.0 A
25 A
24.0 A
32 A
27.0 A
32 A
31.0 A
40 A
35.0 A
40 A
39.0 A
50 A
46.0 A
63 A
46.0 A
63 A
51.0 A
63 A
55.0 A
63 A
59.0 A
80 A
62.0 A
80 A
RYYQ+RYMQ+RXYQ8~20T7Y1B
VRV IV system air conditioner
4P370475-1C – 2016.11