Installation Instruction; Select The Best Location; Wall Mounted - Panasonic CS-NZ9SKE Service Manual

Hide thumbs Also See for CS-NZ9SKE:
Table of Contents

Advertisement

12. Installation Instruction

12.1 Select the Best Location

12.1.1
Indoor Unit
Do not install the unit in excessive oil fume area
such as kitchen, workshop and etc.
There should not be any heat source or steam
near the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Installation height for indoor unit must be at least
2.5 m.
12.1.2
Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
Table A
Piping size
Horse
Std.
Model
Power
Length
(HP)
(m)
Gas Liquid
NZ9***
1.0HP 9.52
6.35
QZ9***
mm
mm
5
"
"
NZ12*** 1.5HP
(3/8
)
(1/4
)
Example: For NZ9***
If the unit is installed at 10 m distance, the quantity of
additional refrigerant should be 50 g .... (10-7.5) m x
20 g/m = 50 g.
A
= (M / (2.5 × (LFL)
min
A
= Required minimum room area, in m
min
M
= Refrigerant charge amount in appliance, in kg
LFL = Lower flammable limit (0.306 kg/m
h
= Installation height of the appliance (1.8 m for
0

wall mounted)

Piping
Addi-
Min.
Max.
Length
Max
tional
Piping
Piping
for
Eleva-
Refri-
Length
Length
add.
tion (m)
gerant
(m)
(m)
gas
(g/m)
(m)
10
3
20
20
7.5
10
3
20
20
7.5
(5/4)
2
× h
))
0
2
3
)
12.1.3
Indoor/Outdoor Unit Installation
Diagram
P
p i
n i
g
i d
e r
t c
o i
n
Right
Right
Rear
Right
bottom
50 mm
or more
Insulation of piping connections
Carry out insulation after
checking for gas leaks and
secure with vinyl tape.
Attaching the remote control holder to the wall
Remote control holder fi xing screws 6
Remote
control 3
Floor
It is advisable to
avoid more than 2
blockage directions.
For better ventilation
& multiple-outdoor
installation, please
consult authorized
Indoor
dealer/specialist.
A
min
2
(m
)
1.12
This illustration is for explanation purposes only.
1.21
The indoor unit will actually face a different way.
29
t A
e t
t n
o i
n
n
t o
o t
b
e
n
d
up drain hose
(Front side)
Flare connection only
at outside of building
Left
(Left and right are identical)
Vinyl tape
Remote control holder 5
WARNING
Installation parts you
should purchase ( )
Installation plate 1
Bushing-Sleeve ( )
Sleeve ( )
Putty ( )
(Gum Type Sealer)
Bend the pipe as
closely on the wall
as possible, but
be careful that it
doesn't break.
Power supply cord
( )
Saddle ( )
Connection cable
Liquid side piping
( )
Gas side piping ( )
Additional drain hose
( )

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs-qz9skeCu-qz9skeCu-nz9skeCs-nz12skeCu-nz12ske

Table of Contents