Advertisement

5.4 FLEXLOGIC™
!"
PATH: SETTINGS
FLEXLOGIC
# LATCH 1
#
The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay
is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as
Autorecloser, until a deliberate HMI action resets the latch. The settings, logic, and element operation are described below:
LATCH 1 TYPE: This setting characterizes Latch 1 to be Set- or Reset-dominant.
LATCH 1 SET: If asserted, the specified FlexLogic™ operands 'sets' Latch 1.
5
LATCH 1 RESET: If asserted, the specified FlexLogic™ operand 'resets' Latch 1.
LATCH N
LATCH N
LATCH N
TYPE
SET
RESET
Reset
ON
Dominant
OFF
ON
OFF
Set
ON
Dominant
ON
OFF
OFF
Figure 5–37: NON-VOLATILE LATCH OPERATION TABLE (N=1 to 16) AND LOGIC
5-74
!"

NON-VOLATILE LATCHES

LATCH 1
FUNCTION: Disabled
LATCH 1 TYPE:
MESSAGE
Reset Dominant
LATCH 1 SET:
MESSAGE
Off
LATCH 1 RESET:
MESSAGE
Off
LATCH 1
MESSAGE
TARGET: Self-reset
LATCH 1
MESSAGE
EVENTS: Disabled
LATCH N
LATCH N
ON
OFF
OFF
ON
OFF
OFF
Previous
Previous
State
State
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
Previous
Previous
State
State
ON
OFF
ON
D60 Line Distance Relay
5.4.8 NON-VOLATILE LATCHES
!
LATCH 1(16)
Range: Disabled, Enabled
Range: Reset Dominant, Set Dominant
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SETTING
SETTING
LATCH 1 FUNCTION:
LATCH 1 TYPE:
Disabled=0
Enabled=1
RUN
SETTING
LATCH 1 SET:
Off=0
SET
SETTING
LATCH 1 SET:
Off=0
RESET
5 SETTINGS
FLEXLOGIC OPERANDS
LATCH 1 ON
LATCH 1 OFF
842005A1.CDR
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents