Dielectric Strength; Control Power - GE D60 Instruction Manual

Line distance relay
Hide thumbs Also See for D60:
Table of Contents

Advertisement

3 HARDWARE
The dielectric strength of the UR-series module hardware is shown in the following table:
Table 3–1: DIELECTRIC STRENGTH OF UR-SERIES MODULE HARDWARE
MODULE
MODULE FUNCTION
TYPE
1
Power Supply
1
Power Supply
1
Power Supply
2
Reserved
3
Reserved
4
Reserved
5
Analog Inputs/Outputs
6
Digital Inputs/Outputs
G.703
7
RS422
8
CT/VT
9
CPU
Filter networks and transient protection clamps are used in module hardware to prevent damage caused by high peak volt-
age transients, radio frequency interference (RFI) and electromagnetic interference (EMI). These protective components
can be damaged by application of the ANSI/IEEE C37.90 specified test voltage for a period longer than the specified one
minute.
CONTROL POWER SUPPLIED TO THE RELAY MUST BE CONNECTED TO THE MATCHING POWER SUPPLY
RANGE OF THE RELAY. IF THE VOLTAGE IS APPLIED TO THE WRONG TERMINALS, DAMAGE MAY
OCCUR!
CAUTION
The D60 relay, like almost all electronic relays, contains electrolytic capacitors. These capacitors are well
known to be subject to deterioration over time if voltage is not applied periodically. Deterioration can be
NOTE
avoided by powering the relays up once a year.
The power supply module can be ordered for two possible voltage ranges. Each range has a dedicated input connection for
proper operation. The ranges are as shown below (see the Technical Specifications section for additional details):
LO range: 24 to 48 V (DC only) nominal
HI range: 125 to 250 V nominal
The power supply module provides power to the relay and supplies power for dry contact input connections.
The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay (see the
Typical Wiring Diagram earlier). The critical failure relay is a Form-C that will be energized once control power is applied
and the relay has successfully booted up with no critical self-test failures. If on-going self-test diagnostic checks detect a
critical failure (see the Self-Test Errors table in Chapter 7) or control power is lost, the relay will de-energize.
GE Multilin
TERMINALS
FROM
High (+); Low (+); (–)
48 V DC (+) and (–)
Relay Terminals
N/A
N/A
N/A
All except 8b
All (See Precaution 2)
All except 2b, 3a, 7b, 8a
All except 6a, 7b, 8a
All
All
D60 Line Distance Relay

3.2.2 DIELECTRIC STRENGTH

DIELECTRIC STRENGTH
(AC)
TO
Chassis
2000 V AC for 1 minute
Chassis
2000 V AC for 1 minute
Chassis
2000 V AC for 1 minute
N/A
N/A
N/A
N/A
N/A
N/A
Chassis
< 50 V DC
Chassis
2000 V AC for 1 minute
Chassis
2000 V AC for 1 minute
Chassis
< 50 V DC
Chassis
2000 V AC for 1 minute
Chassis
2000 V AC for 1 minute

3.2.3 CONTROL POWER

3.2 WIRING
3
3-7