GE D60 Instruction Manual page 172

Line distance relay
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5.5 GROUPED ELEMENTS
5
The ground mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, current, and phase selection supervising characteristics. The ground quadrilateral distance function is com-
posed of a reactance characteristic, right and left blinders, and 100% memory-polarized directional, overcurrent, and phase
selection supervising characteristics.
When set to non-directional, the mho function becomes an offset mho with the reverse reach controlled independently from
the forward reach, and all the directional characteristics removed. When set to non-directional, the quadrilateral function
applies a reactance line in the reverse direction instead of the directional comparators.
The reactance supervision for the mho function uses the zero-sequence current for polarization. The reactance line of the
quadrilateral function uses either zero-sequence or negative-sequence current as a polarizing quantity. The selection is
controlled by a user setting and depends on the degree of non-homogeneity of the zero-sequence and negative-sequence
equivalent networks.
The directional supervision uses memory voltage as polarizing quantity and both zero- and negative-sequence currents as
operating quantities.
5-88
GND DIST Z1 REV
MESSAGE
REACH: 2.00 Ω
GND DIST Z1 REV
MESSAGE
REACH RCA: 85°
GND DIST Z1 POL
MESSAGE
CURRENT: Zero-seq
GND DIST Z1 NON-
MESSAGE
HOMOGEN ANG: 0.0°
GND DIST Z1
MESSAGE
COMP LIMIT: 90°
GND DIST Z1
MESSAGE
DIR RCA: 85°
GND DIST Z1
MESSAGE
DIR COMP LIMIT: 90°
GND DIST Z1 QUAD
MESSAGE
RGT BLD: 10.00 Ω
GND DIST Z1 QUAD
MESSAGE
RGT BLD RCA: 85°
GND DIST Z1 QUAD
MESSAGE
LFT BLD: 10.00 Ω
GND DIST Z1 QUAD
MESSAGE
LFT BLD RCA: 85°
GND DIST Z1
MESSAGE
SUPV: 0.200 pu
GND DIST Z1 VOLT
MESSAGE
LEVEL: 0.000 pu
GND DIST Z1
MESSAGE
DELAY:0.000 s
GND DIST Z1 BLK:
MESSAGE
Off
GND DIST Z1
MESSAGE
TARGET: Self-Reset
GND DIST Z1
MESSAGE
EVENTS: Disabled
D60 Line Distance Relay
Range: 0.02 to 250.00
in steps of 0.01
Range: 30 to 90° in steps of 1
Range: Zero-seq, Neg-seq
Range: –40.0 to 40.0° in steps of 0.1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 0.02 to 500.00
in steps of 0.01
Range: 60 to 90° in steps of 1
Range: 0.02 to 500.00
in steps of 0.01
Range: 60 to 90° in steps of 1
Range: 0.050 to 30.000 pu in steps of 0.001
Range: 0.000 to 5.000 pu in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
Range: Self-Rest, Latched, Disabled
Range: Disabled, Enabled