GE D60 Instruction Manual page 179

Line distance relay
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5 SETTINGS
!"
PATH: SETTINGS
GROUPED ELEMENTS
# POWER SWING
# DETECT
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
!
!"
SETTING GROUP 1(6)
POWER SWING DETECT
POWER SWING
FUNCTION: Disabled
POWER SWING
SOURCE: SRC 1
POWER SWING
SHAPE: Mho Shape
POWER SWING
MODE: Two Step
POWER SWING
SUPV: 0.600 pu
POWER SWING FWD
REACH: 50.00 Ω
POWER SWING QUAD FWD
REACH MID: 60.00 Ω
POWER SWING QUAD FWD
REACH OUT: 70.00 Ω
POWER SWING FWD
RCA: 75°
POWER SWING REV
REACH: 50.00 Ω
POWER SWING QUAD REV
REACH MID: 60.00 Ω
POWER SWING QUAD REV
REACH OUT: 70.00 Ω
POWER SWING REV
RCA: 75°
POWER SWING OUTER
LIMIT ANGLE: 120°
POWER SWING MIDDLE
LIMIT ANGLE: 90°
POWER SWING INNER
LIMIT ANGLE: 60°
POWER SWING OUTER
RGT BLD: 100.00 Ω
POWER SWING OUTER
LFT BLD: 100.00 Ω
POWER SWING MIDDLE
RGT BLD: 100.00 Ω
POWER SWING MIDDLE
LFT BLD: 100.00 Ω
POWER SWING INNER
RGT BLD: 100.00 Ω
D60 Line Distance Relay
5.5 GROUPED ELEMENTS
5.5.5 POWER SWING DETECT
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: Mho Shape, Quad Shape
Range: Two Step, Three Step
Range: 0.050 to 30.000 pu in steps of 0.001
Range: 0.10 to 500.00
in steps of 0.01
Range: 0.10 to 500.00
in steps of 0.01
Range: 0.10 to 500.00
in steps of 0.01
Range: 40 to 90° in steps of 1
Range: 0.10 to 500.00
in steps of 0.01
Range: 0.10 to 500.00
in steps of 0.01
Range: 0.10 to 500.00
in steps of 0.01
Range: 40 to 90° in steps of 1
Range: 40 to 140° in steps of 1
Range: 40 to 140° in steps of 1
Range: 40 to 140° in steps of 1
Range: 0.10 to 500.00
in steps of 0.01
Range: 0.10 to 500.00
in steps of 0.01
Range: 0.10 to 500.00
in steps of 0.01
Range: 0.10 to 500.00
in steps of 0.01
Range: 0.10 to 500.00
in steps of 0.01
5
5-95

Advertisement

Table of Contents
loading

Table of Contents