Communications - GE D60 Instruction Manual

Line distance relay
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5 SETTINGS
a) MAIN MENU
!
PATH: SETTINGS
PRODUCT SETUP

# COMMUNICATIONS

#
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
b) SERIAL PORTS
!
PATH: SETTINGS
PRODUCT SETUP
# SERIAL PORTS
#
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The D60 is equipped with up to 3 independent serial communication ports. The faceplate RS232 port is intended for local
use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet or
RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important that
these parameters agree with the settings used on the computer or other equipment that is connected to these ports. Any of
these ports may be connected to a computer running EnerVista UR Setup. This software can download and upload setting
files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and con-
nected to a DCS, PLC or PC using the RS485 ports.
For each RS485 port, the minimum time before the port will transmit after receiving data from a host can be
set. This feature allows operation with hosts which hold the RS485 transmitter active for some time after
each transmission.
NOTE
GE Multilin
!"
COMMUNICATIONS
# SERIAL PORTS
#
# NETWORK
#
# MODBUS PROTOCOL
#
# DNP PROTOCOL
#
# IEC 61850 PROTOCOL
#
# WEB SERVER
# HTTP PROTOCOL
# TFTP PROTOCOL
#
# IEC 60870-5-104
# PROTOCOL
# SNTP PROTOCOL
#
!"
!
COMMUNICATIONS
SERIAL PORTS
RS485 COM1 BAUD
RATE: 19200
RS485 COM1 PARITY:
None
RS485 COM1 RESPONSE
MIN TIME:
0 ms
RS485 COM2 BAUD
RATE: 19200
RS485 COM2 PARITY:
None
RS485 COM2 RESPONSE
MIN TIME:
0 ms
D60 Line Distance Relay
5.2 PRODUCT SETUP
5.2.4 COMMUNICATIONS
See below.
See page 5–12.
See page 5–12.
See page 5–13.
See page 5–15.
See page 5–17.
See page 5–18.
See page 5–18.
See page 5–19.
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200. Only
active if CPU 9E is ordered.
Range: None, Odd, Even
Only active if CPU Type 9E is ordered
Range: 0 to 1000 ms in steps of 10
Only active if CPU Type 9E is ordered
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200
Range: None, Odd, Even
Range: 0 to 1000 ms in steps of 10