GE D60 Instruction Manual page 391

Line distance relay
Hide thumbs Also See for D60:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 10 of 43)
ADDR
REGISTER NAME
409A
DNP Port
409B
DNP Address
409C
DNP Client Addresses (2 items)
40A0
TCP Port Number for the Modbus protocol
40A1
TCP/UDP Port Number for the DNP Protocol
40A3
TCP Port Number for the HTTP (Web Server) Protocol
40A4
Main UDP Port Number for the TFTP Protocol
40A5
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means "automatic") (2 items)
40A7
DNP Unsolicited Responses Function
40A8
DNP Unsolicited Responses Timeout
40A9
DNP Unsolicited Responses Max Retries
40AA
DNP Unsolicited Responses Destination Address
40AB
Ethernet Operation Mode
40AC
DNP User Map Function
40AD
DNP Number of Sources used in Analog points list
40AE
DNP Current Scale Factor
40AF
DNP Voltage Scale Factor
40B0
DNP Power Scale Factor
40B1
DNP Energy Scale Factor
40B2
DNP Other Scale Factor
40B3
DNP Current Default Deadband
40B4
DNP Voltage Default Deadband
40B5
DNP Power Default Deadband
40B6
DNP Energy Default Deadband
40B7
DNP Other Default Deadband
40B8
DNP IIN Time Sync Bit Period
40B9
DNP Message Fragment Size
40BA
DNP Client Address 3
40BC
DNP Client Address 4
40BE
DNP Client Address 5
40C0
DNP Number of Paired Binary Output Control Points
40C1
Reserved (31 items)
40E0
TCP Port Number for the IEC 60870-5-104 Protocol
40E1
IEC 60870-5-104 Protocol Function
40E2
IEC 60870-5-104 Protocol Common Address of ASDU
40E3
IEC 60870-5-104 Protocol Cyclic Data Trans. Period
40E4
IEC 60870-5-104 Sources used in M_ME_NC_1 point list
40E5
IEC 60870-5-104 Current Default Threshold
40E6
IEC 60870-5-104 Voltage Default Threshold
40E7
IEC 60870-5-104 Power Default Threshold
40E8
IEC 60870-5-104 Energy Default Threshold
40E9
IEC 60870-5-104 Other Default Threshold
40EA
IEC 60870-5-104 Client Address (5 items)
40FE
IEC 60870-5-104 Communications Reserved (2 items)
4100
DNP Binary Input Block of 16 Points (58 items)
4140
DNP Object 1 Default Variation
4141
DNP Object 2 Default Variation
4142
DNP Object 20 Default Variation
4143
DNP Object 21 Default Variation
4144
DNP Object 22 Default Variation
4145
DNP Object 23 Default Variation
4146
DNP Object 30 Default Variation
4147
DNP Object 32 Default Variation
GE Multilin
RANGE
0 to 4
0 to 65519
0 to 4294967295
1 to 65535
1 to 65535
1 to 65535
1 to 65535
0 to 65535
0 to 1
0 to 60
1 to 255
0 to 65519
0 to 1
0 to 1
1 to 6
0 to 8
0 to 8
0 to 8
0 to 8
0 to 8
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
1 to 10080
30 to 2048
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 16
0 to 1
1 to 65535
0 to 1
0 to 65535
1 to 65535
1 to 6
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 4294967295
0 to 1
0 to 58
1 to 2
1 to 2
0 to 3
0 to 3
0 to 3
0 to 3
1 to 5
0 to 5
D60 Line Distance Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F177
---
1
F001
---
1
F003
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F102
s
1
F001
---
1
F001
---
1
F001
---
1
F192
---
1
F102
---
1
F001
---
1
F194
---
1
F194
---
1
F194
---
1
F194
---
1
F194
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
min
1
F001
---
1
F001
---
1
F003
---
1
F003
---
1
F003
---
1
F001
---
1
F001
---
1
F001
---
1
F102
---
1
F001
s
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F003
---
1
F001
---
1
F197
---
1
F001
---
1
F001
---
1
F523
---
1
F524
---
1
F523
---
1
F523
---
1
F001
---
1
F525
DEFAULT
0 (None)
1
0
502
20000
B
80
69
0
0 (Disabled)
5
10
1
0 (Half-Duplex)
0 (Disabled)
1
2 (1)
2 (1)
2 (1)
2 (1)
2 (1)
30000
30000
30000
30000
30000
1440
240
0
0
0
0
0
2404
0 (Disabled)
0
60
1
30000
30000
30000
30000
30000
0
0
0 (Not Used)
2
2
0 (1)
0 (1)
0 (1)
0 (1)
1
0 (1)
B-17

Advertisement

Table of Contents
loading

Table of Contents