• Do not common vent or connect any vent from other appliances to the water heater vent.
General rules for vent terminations:
• Avoid locating the water heater vent termination near any air intake devices. These fans can
pick up the exhaust flue products from the water heater and return them to the building. This
can create a health hazard.
• Locate the vent termination so that it cannot be blocked by any debris, at any time. Most codes
require that the termination must be at least 12 in. (305 mm) above grade and anticipated snow
line, but the installer may determine if it should be higher depending on the job site condition
and applicable codes.
• A proper sidewall termination is required when the water heater is vented through a sidewall.
• Regarding the clearances from the exhaust termination to the air inlet or opening, refer to
pp. 21 to 23.
Approved Category III, Single Wall, Stainless Steel Venting Suppliers and Part Numbers
WARNING! Do not mix parts or fittings of different material types, and do not mix pipe, fittings, or
joining methods from different manufacturers. Combustion exhaust can contain carbon monoxide and
must be properly vented outside. Breathing abnormal amounts of carbon monoxide can result in seri-
ous injury or death.
Description
4" Straight pipe - 6" length
4" Straight pipe - 12" length
4" Straight pipe - 24" length
4" Straight pipe - 36" length
4" Straight pipe - 48" length
4" Adjustable straight pipe - 10"-18" adjustability
4" 45 degree elbow
4" 90 degree elbow
4" Sidewall termination (4"Termination Hood)
4" Vent termination tee
4" Rain Cap
4" Extreme weather rain cap
4" Horizontal drain tee
4" Vertical drain tee
4" wall thimble length 4"-7" wall thickness
4" wall thimble length 5"-10" wall thickness
4" 3-in-1 adaptor (F-F adaptor, condensate
drain, & back-flow preventer)
4" F-F adaptor
4" Backflow preventer w/ F-F adaptor
4" exhaust / 3" intake DV concentric termina-
tion - 5"-10" adjustability
4" exhaust / 3" intake DV concentric termina-
tion - 12"-18" adjustability
4" Sidewall termination, adjustable pipe
4" Wall Thimble, 3"-6" wall thickness
Heater Vent Kits
NovaVENT™
100112407
100112406
100112404
100112403
100112402
100112405
100112401
100112400
100112419
100112547
100112415
100112548
100112414
100112413
100112732
100112733
100112585
100112399
100112416
100112550
2NVHTC43S
100112551
100187853
100187852
14
Page
Installation Manual
Installation
Z-FLEX®
Z-VENT™
2NVP4.5
2SVEPWCF0406
2NVP41
2SVEPWCF0401
2NVP42
2SVEPWCF0402
2NVP43
2SVEPWCF0403
2NVP44
2SVEPWCF0404
2NVAL4
2SVSPA04
2NVE445
2SVEEWCF0445
2NVE490
2SVEEWCF0490
2NVHTX4
2SVSHTX04
2NVTT4
2SVSTTF04
2NVRC4
2SVSRCF04
2NVWC4
2SVSHRC04
2NVHD4
2SVEDWCF04
2NVVD4
2SVEVDP04
2NVWT4
2SVSWTF04
2NVWT4L
2SVSWTEF04
2NVBFA4
2SVBFDPA04
2NVAFF4
2SVEEWCF0445
2NVBFU4
2ZVB04
2SVSHTC43S
2NVHTC43
2SVSHTC43
2NVBV4
n/a
2NVBT4
n/a

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

310 outdoor310 indoor510 outdoor510 indoor

Table of Contents