According to EN 61800-3 filters are not needed in industrial zone (Second
Environment) for DCS800 drives above 100 A rated current. For rated currents
below 100 A the filter requirement is identical to Light Industry (First Environment).

Three-phase filters

EMC filters are necessary to fulfil the standard for emitted interference if a converter
shall be run at a public low voltage line, in Europe for example with 400 V between
the phases. Such lines have a grounded neutral conductor. ABB offers suitable
three-phase filters for 400 V and 25 A...600 A and 500 V filters for 440 V lines
outside Europe. The filters can be optimized for the real motor currents:
I
Filter
Lines with 500 V to 1000 V are not public. They are local networks inside factories,
and they do not supply sensitive electronics. Therefore converters do not need EMC
filters if they shall run with 500 V and more.
Type of converter
2-Q Converter
DCS800-S01-0020-0y
DCS800-S01-0045-0y
DCS800-S01-0065-0y
DCS800-S01-0090-0y
DCS800-S01-0125-0y
DCS800-S01-0180-0y
DCS800-S01-0230-0y
DCS800-S01-0315-0y
DCS800-S01-0405-0y
DCS800-S01-0500-0y
DCS800-S01-0610-0y
DCS800-S01-0740-0y
DCS800-S01-0900-0y
DCS800-S01-0900-0y
DCS800-S01-1200-0y
DCS800-S01-1500-0y
DCS800-S01-2000-0y
➀ Filter only available on request
= 0.8 • I
; the factor 0.8 respects the current ripple.
MOT max
IDC [A]
4-Q Converter
20A
DCS800-S02-0025-0y
45A
DCS800-S02-0050-0y
65A
DCS800-S02-0075-0y
90A
DCS800-S02-0100-0y
125A
DCS800-S02-0140-0y
180A
DCS800-S02-0200-0y
230A
DCS800-S02-0260-0y
315A
DCS800-S02-0350-0y
405A
DCS800-S02-0450-0y
500A
DCS800-S02-0550-0y
610A
DCS800-S02-0680-0y
740A
DCS800-S02-0820-0y
900A
DCS800-S02-1000-0y
900A
DCS800-S02-0900-0y
1200A
DCS800-S02-1200-0y
1500A
DCS800-S02-1500-0y
2000A
DCS800-S02-2000-0y
≤ 3000A
3ADW000194R0201 DCS800 Hardware Manual e b
Constr.
Filter type f. y=4
type
IDC [A]
25A
D1
NF3-440-25
50A
D1
NF3-440-50
75A
D1
NF3-440-64
100A
D1
NF3-440-80
140A
D1
NF3-440-110
200A
D2
NF3-500-320
260A
D2
NF3-500-320
350A
D3
NF3-500-320
450A
D3
NF3-500-600
550A
D3
NF3-500-600
680A
D4
NF3-500-600
D4
NF3-500-600
NF3-690-1000 ➀ NF3-690-1000 ➀
820A
D4
NF3-690-1000 ➀ NF3-690-1000 ➀
1000A
D4
NF3-690-1000 ➀ NF3-690-1000 ➀
900A
D5
NF3-690-1000 ➀ NF3-690-1000 ➀
1200A
D5
NF3-690-1600 ➀ NF3-690-1600 ➀
1500A
D5
NF3-690-1600 ➀ NF3-690-1600 ➀
2000A
D5
≤ 3000A
NF3-690-2500 ➀ NF3-690-2500 ➀
D6
Planning the electrical installation
33
Filter type f. y= 5
NF3-500-25
NF3-500-50
NF3-500-64
NF3-500-80
NF3-500-110
NF3-500-320
NF3-500-320
NF3-500-320
NF3-500-600
NF3-500-600
NF3-500-600
NF3-500-600