The distance between pulse encoder and interface board is dependent on the
voltage drop on the connecting lines and on the output and input configuration of the
used components. If cables are used according to the table below the voltage drop
caused by the cable can be compensated by the voltage regulator.
Cable length
parallel wires for
power source & GND
0 ... 50 m
1x 0.25 mm²
50 ... 100 m
2x 0.25 mm²
100 ... 150 m
3x 0.25 mm²
3ADW000194R0201 DCS800 Hardware Manual e b
Cable used
12x 0.25 mm²
12x 0.25 mm²
14x 0.25 mm²
57
Electrical installation