Disturbance Factors At Thermographic Inspection Of Electrical Installations; Wind; Rain And Snow - FLIR E series User Manual

Hide thumbs Also See for E series:
Table of Contents

Advertisement

28 – Introduction to thermographic inspections of electrical installations
28.6
Disturbance factors at thermographic inspection of
electrical installations
During thermographic inspections of different types of electrical installations, distur-
bance factors such as wind, distance to object, rain or snow often influence the
measurement result.
28.6.1

Wind

During outdoor inspection, the cooling effect of the wind should be taken into account.
An overheating measured at a wind velocity of 5 m/s (10 knots) will be approximately
twice as high at 1 m/s (2 knots). An excess temperature measured at 8 m/s (16 knots)
will be 2.5 times as high at 1 m/s (2 knots). This correction factor, which is based on
empirical measurements, is usually applicable up to 8 m/s (16 knots).
There are, however, cases when you have to inspect even if the wind is stronger than
8 m/s (16 knots). There are many windy places in the world, islands, mountains, and
so on but it is important to know that overheated components found would have
shown a considerably higher temperature at a lower wind speed. The empirical cor-
rection factor can be listed.
Wind speed (m/s)
1
2
3
4
5
6
7
8
The measured overheating multiplied by the correction factor gives the excess tem-
perature with no wind, that is, at 1 m/s (2 knots).
28.6.2

Rain and snow

Rain and snow also have a cooling effect on electrical equipment. Thermographic
measurement can still be conducted with satisfactory results during light snowfall
with dry snow and light drizzle, respectively. The image quality will deteriorate in heavy
146
Wind speed (knots)
2
4
6
8
10
12
14
16
Publ. No. T559597 Rev. a554 – ENGLISH (EN) – September 27, 2011
Correction factor
1
1.36
1.64
1.86
2.06
2.23
2.40
2.54

Advertisement

Table of Contents
loading

Table of Contents