Restore Calibration - Honeywell XYR 6000 User Manual

Temperature
Hide thumbs Also See for XYR 6000:
Table of Contents

Advertisement

Restore calibration

Step
1
In Wireless Builder, set the transmitter's channel to OOS (Out of Service).
2
In Wireless Builder, set the transmitter's Write Lock to Unlocked.
3
At the transmitter display, verify the channel's PV value is followed by an out of service (OUT
SVC) message.
Use Authentication Device's Device Local Configuration buttons to navigate to the transmitter's
CAL menu.
If CAL menu is passcode protected, enter the passcode.
If the channel is not out of service a WRONG MODE message will be displayed. Go to step 1.
If the transmitter is locked a LOCKED message will be displayed. Go to step 2.
4
Select the channel (CH 1, CH 2 or CH 3).
Select CAL RSTR
Press Enter to continue.
Display will say BUSY, then SUCCESS.
If unsuccessful the display will show BAD_FACTORY_CALIBRATION.
5
When ready, in Wireless Builder return the transmitter's channel to service and set Write Lock
to Locked.
Revision 2
8/7/07
OneWireless XYR 6000 Temperature Transmitter User's Manual
3.4. Calibrating the transmitter
Action
3. Preparation
9

Advertisement

Table of Contents
loading

Table of Contents