3. Preparation
3.4. Calibrating the transmitter

Clear calibration

Step
1
In Wireless Builder, set the transmitter's channel to OOS (Out of Service).
2
In Wireless Builder, set the transmitter's Write Lock to Unlocked.
3
At the transmitter display, verify the channel's PV value is followed by an out of service (OUT
SVC) message.
Use Authentication Device's Device Local Configuration buttons to navigate to the transmitter's
CAL menu.
If CAL menu is passcode protected, enter the passcode.
If the channel is not out of service a WRONG MODE message will be displayed. Go to step 1.
If the transmitter is locked a LOCKED message will be displayed. Go to step 2.
4
Select the channel (CH 1, CH 2 or CH 3).
Select CAL CLR
Press Enter to continue.
Display will say BUSY, then SUCCESS.
Repeat for each channel desired.
5
When ready, in Wireless Builder return the transmitter's channel to service and set Write Lock
to Locked.
10
OneWireless XYR 6000 Temperature Transmitter User's Manual
Action
Revision 2
8/7/07