Description, device design, dimension drawing
2.7 Setting the switch-on delay time
2.7.2
SITOP PSE200U
Figure 2-15
Setting the sequential switch-on delay
The switch-on delay is set at selector switch
are in position "0" (no switch-on delay).
Procedure when setting the delay time:
With the selectivity module in a no-voltage condition, set DIP switches "A" and "B" to the
required delay time.
The next time that the selectivity module powers up, the outputs are sequentially switched on
corresponding to the selected delay time.
28
SITOP PSE200U selector switch
No delay, all four outputs are simultaneously switched-on (condition when delivered).
25 ms delay between the outputs being switched on.
100 ms delay between the outputs being switched on.
Outputs switched on depending on the load: The next output is switched on as soon as the
current of the previous output lies below the selected response threshold.
⑪
. When delivered, DIP switches "A" and "B"
Manual, 01.2017, C98130-A7579-A1-2-7629
Selectivity modules