Description, device design, dimension drawing
2.5 Buttons and selector switches
2.5.2

SITOP PSE200U

Figure 2-7
The button
1. manually switching an output off and on (see the following).
2. resetting an output automatically switched off due to an overload condition (see Chapter
Electronic overload shutdown and reset (Page 21)).
The selector switch
outputs (see Chapter Setting the switch-on delay time (Page 26)).
Manually switching an output on and off
An individual output can be switched on and switched off using the button. When the device
is delivered, the outputs are manually switched off.
Switching off an output:
For outputs that are switched on, LED
off the output by pressing the assigned button
been manually switched off).
Switching on an output:
For outputs that have been manually switched off, LED
orange. You can switch on the output by pressing the assigned button
lit green (output is switched on).
Note
An output that has been manually switched-off can only be manually switched-on again by
manually pressing the button again. It is not possible to switch on an output that has been
manually switched off using the remote reset signal.
An output that has been manually switched off remains saved (latch) even when the supply
voltage is no longer available, and is a manually switched off when the supply voltage
returns.
20
Buttons and selector switches, SITOP PSE200U
for the SITOP PSE200U selectivity module has the following two functions:
can be used to select the delay time when switching on the individual
of the particular output is lit green. You can switch
. The LED then flashes orange (output has
of the particular output is lit
Manual, 01.2017, C98130-A7579-A1-2-7629
. The LED is then
Selectivity modules