Siemens SITOP Manual page 49

Hide thumbs Also See for SITOP:
Table of Contents

Advertisement

Shutdown characteristics SITOP PSE200U (with the exception of -2BA51, -2BA61) product
version 1:
Figure 6-2
● An output current is continuously permissible up to the selected current response
threshold.
● In the range 101 - 129 % of the selected current response threshold, an overload current
is permissible for 5 seconds; after this time, the output is electronically shut down.
130 %; typically after 100 ms the output is electronically shut down.
● When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically
shutdown.
Shutdown characteristics SITOP PSE200U (with the exception of -2BA51, -2BA61) from
product version 2 and higher:
Figure 6-3
● An output current is continuously permissible up to the selected current response
threshold.
● In the range 101 - 149 % of the selected current response threshold, an overload current
is permissible for 5 seconds; after this time, the output is electronically shut down.
Selectivity modules
Manual, 01.2017, C98130-A7579-A1-2-7629
Shutdown characteristics SITOP PSE200U (product version 1)
In the range > 130 % of the selected current response threshold, the current is limited to
Shutdown characteristics SITOP PSE200U (from product version 2 and higher)
Technical data
6.2 Output
49

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitop pse200u

Table of Contents