Mounting position, mounting clearances

4.1

Standard mounting position

The device is mounted on standard mounting rails. The device must be mounted vertically in
such a way that the input terminals are at the bottom.
A clearance of at least 50 mm should be maintained above and below the device (maximum
depth of the cable duct, 50 mm).
No space is required at the side.
Individual output current as a function of the ambient temperature and installation altitude
Figure 4-1
Figure 4-2
Selectivity modules
Manual, 01.2017, C98130-A7579-A1-2-7629
6EP1961-2BA00: Output current in the standard mounting position
6EP1961-2BA11, 6EP1961-2BA31, 6EP1961-2BA51 and 6EP1961-2BA61 output
current in the standard mounting position