Limitless™ Series WLS Limit Switch
Figure 5. WLS Single Switch Adapter BT3 & BT4 user-
supplied switch term & wires
4.3 WLS Non-Contact Switch Series Operation
The WLS Non-Contact Switch contains a reed switch that requires a magnetic actuator to operate. The WPMM or WDRR Series moni-
tor/receiver output changes state with the presence and absence of the magnetic actuator. The chosen magnetic actuator will affect
the operating characteristics of the WLS Non-Contact Switch (i.e., operating point and release point). The WLS Non-Contact Switch is
supplied with a WMG1 magnetic actuator that offers a 0.150 in min. operating point and 0.600 in release point when used in a head-
on actuation mode (see Figure 7). Honeywell magnet, WMG2, offers a 0.45 in min. operating point and 1.0 in release point when used
in a head-on actuation mode. The user may choose his/her magnetic actuator that needs to be tested in the application to determine
suitable operating characteristics.
Another common type of actuation mode is "slide-by," that requires set-up and testing in the user's application to determine suitability
(see Figure 8). The gap between the WLS Non-Contact Switch head and magnet can be varied via trial testing to achieve a suitable
operating point and release point for the application.
Set-up/Information tips (The user will need to test chosen magnet(s) and actuation mode(s) against the actual application conditions
to prove suitability):
Center the magnet actuator with the center of the red target on the WLS Non-Contact Switch head
Position the magnet to be parallel to the WLS Non-Contact Switch head
Surrounding ferrous metal or magnetic fields in the application may affect the operating characteristics and desired functionality
Temperature changes affect operating characteristics
Do not apply excessive shock to the WLS Non-Contact Switch
Do not expose the WLS Non-Contact Switch or magnetic actuators to excessively large magnetic fields
Figure 6. WLS Single Switch Adapter BT3 & BT4 inter-
nal connector terminals and user-supplied wires