2 Operation

Following are the approved applications for the NFS2-3030:
NOTE: When operating as a Protected Premises Control Unit, the ONYXWORKS-WS is UL Listed for monitoring and control of fire, smoke
control, and mass notification devices.
Local Application
– Emergency Relocation (paging, live and pre-recorded)
– Emergency Communication (telephone)
Protected premises unit
– Auxiliary
– Central Station
– Remote Station
– Proprietary
– Proprietary (Rec unit)
Communication transmission path
– Coded
– Non-coded
– DACT, no line security
– Reverse Polarity
– Other transmission technologies, no line security
Releasing
– Cross Zone
– NFPA 12 Co2 Fire Extinguishing Systems
– NFPA 12A, Halon 1301 Fire Extinguishing Systems
– NFPA 13, Sprinkler Systems
– NFPA 15, Water Spray Systems
– NFPA 16, Foam-water sprinkler and foam-water spray systems
– NFPA 17, Dry Chemical Extinguishing Systems
– NFPA 17A, Wet Chemical Extinguishing Systems
– NFPA 72 Central Station (Automatic, Manual and Waterflow) Fire Alarm Systems
– NFPA 72 Local (Automatic, Manual, Waterflow, and Sprinkler Supervisory) Fire Alarm Systems
– NFPA 72 Auxiliary (Automatic, Manual and Waterflow) Fire Alarm Systems
– NFPA 72 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Systems
– NFPA 72 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems (Protected Premises Unit)
– NFPA 2001, Clean Agent Fire Extinguishing Systems
Process Control, Non-critical
Regional Settings
– Canada (see "Canadian Applications" on page 26)
– Chicago
• Panel's Drill and Signal Silence keys will not function
• Annunciator Control Modules and SLC modules given a drill or signal silence Mode or Type Code will not allow local drill or signal
silence initiation
• Events must be Acknowledged prior to system reset
Fire Alarm Event
– Initiating Device Activation
• Produces a steady audible tone
• Turns on the Alarm relay(s) (TB4, TB1 and TB2, if switch enabled)
• Flashes the
FIRE ALARM
• Displays a Type Code that indicates the type of fire alarm being generated
• Latches the control panel in alarm (condition must be corrected and a reset performed to clear the alarm state from the panel)
• Activates the General Alarm zone (Z000)
• Displays
FIRE ALARM
• Sends an Alarm message to the LCD display, remote annunciators, history buffer, installed printers, and CRT-2s
• Initiates any Control-By-Event actions
• Starts timers such as Silence Inhibit and Auto Silence
• Sends a Alarm message to the proprietary receiver via the network, if applicable
NOTE: If the alarm event is initiated by a device with a waterflow type Code, the control panel will disable the Signal Silence key
and the Auto Silence Timer.
20
LED (red)
in the status banner on the control panel, along with information specific to the device