Honeywell 50054911 Installation Manual page 26

Limitless series wls limit switch
Table of Contents

Advertisement

Limitless™ Series WLS Limit Switch
Pairing Steps when using a WDRR (see Figure 13): The battery will need to be activated in the WLS and proper power applied to
the WDRR (green  LED illuminated) before proceeding with this pairing procedure. Once the pairing is completed, the WLS selected
will only communicate with the WDRR it was paired to and no other device.
Step
Action
1
Completely read this procedure before starting in order to understand the timing of events that need to be performed.
2
WLS: Remove (if required) the two screws  on the housing cover (See Figure 11, page 21) of the WLS and locate the
function button  (see Figure 10) to be used in Step 4.
3
WDRR: Press the Function button  on WDRR (See Figure 15, page 23) for more than four seconds and less than eight
seconds at which time the green and yellow LEDs  (see Figure 14, page 21) will be flashing which indicates to release
the function button immediately as it has entered the pairing mode.
4
WLS: Within a 30 second interval of Step 3, depress the WLS function button  (See Figure 13, page 21) and hold de-
pressed for more than one second and less than 12 seconds at which time the orange LED turns on (see Figure 12,
page 21). While in pairing mode, the orange  LED will flash on for 100 ms every second. The orange  LED flashes three
times 100 ms on, 100 ms off when pairing succeeds. If pairing does not succeed, the orange LED will turn off and user
will need to repeat steps starting with Step 3.
5
WDRR Receiver: Successful pairing will be indicated by the green and yellow LEDs  (see Figure 15, page 23) ceasing to
flash and remaining on for a few seconds before turning off. The specific Tricolor Output LED will also turn on.
6
To confirm proper pairing between the WLS and WDRR: actuate the WLS actuator, actuate using the magnetic actuator
(WLS Non-Contact Switch only), or actuate the user supplied switch for the WLS Single Switch Adapter, and the Tricolor
Output LED  (see Figure 15, page 23) should turn on to indicate the proper output status.
7
Record the WLS Sequence # on identification labels † and apply to the WLS actuator or WLS housing in desired locations
(See Figure 14, page 21).
8
Repeat Steps 2-7 to add additional Limitless™ switch. Up to 14 WLS can be paired to a single WDRR.
22
Honeywell Sensing and Control
50054911
ISSUE 3