The figures in brackets refer to the following illustrations.
On the electronics module you will find the following display and

adjustment elements:

Potentiometer for adjustment of the density range (1)
DIL switch for mode adjustment - min./max. (2)
Simulation key (3)
Signal lamp (6)
6.2
Adjustment elements
6
5
Fig. 12: Electronics and connection compartment - NAMUR output
1
Potentiometer for adjustment of the density range
2
DIL switch for characteristics reversal
3
Simulation key
4
Ground terminal
5
Connection terminals
6
Control lamp
With the potentiometer you can adapt the switching point to the solid.
It is already preset and must only be modified in special cases.
As a default setting, the potentiometer of VEGAVIB 63 is set to
the complete right position (> 0.3 g/cm³/0.011 lbs/in³). In very light
solids you have to turn the potentiometer to the complete left posi-
tion (0.02 ... 0.1 g/cm³ or 0.0007 ... 0.0036 lbs/in³). By doing this,
VEGAVIB 63 will be more sensitive and light solids can be detected
more reliably.
For instruments detecting solids in water, these settings are not ap-
plicable. The density range is preset and must not be changed.