GE 239 Instruction Manual page 86

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

SEE PREVIOUS PAGE
] SWITCH INPUTS
] SIMULATION
MESSAGE
MESSAGE
] THERMISTOR
] SIMULATION
MESSAGE
MESSAGE
] RTD SIMULATION
]
MESSAGE
MESSAGE
] GE POWER MANAGEMENT
] USE ONLY
4–50
Courtesy of NationalSwitchgear.com
MESSAGE
SIMULATION: OFF
SIMULATION ENABLED
MESSAGE
FOR: 15 min
EMERGENCY RESTART
INPUT: OPEN
EXTERNAL RESET
INPUT: OPEN
OPTION SWITCH 1
INPUT: OPEN
OPTION SWITCH 2
INPUT: OPEN
MESSAGE
SIMULATION:
OFF
SIMULATION ENABLED
MESSAGE
FOR: 15 min
THERMISTOR
RESISTANCE: 0 Ω
MESSAGE
SIMULATION:
OFF
SIMULATION ENABLED
MESSAGE
FOR: 15 min
RTD 1 TEMPERATURE:
0 °C
RTD 2 TEMPERATURE:
0 °C
RTD 3 TEMPERATURE:
0 °C
SERVICE PASSCODE:
0
FIGURE 4–8: Setpoints Page 5 – Testing
CHAPTER 4: PROGRAMMING
Range: OFF, ON
Range: 5 to 300, UNLIMITED
Step: 5 min.
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: ON, OFF
Range: 5 to 300, UNLIMITED
Step: 5 min.
Range: 0 to 30000
Step: 1 Ω
Range: OFF, ON
Range: 5 to 300, UNLIMITED
Step: 5 min.
Range: –40 to +200 step 1°C (if °C)
–40 to +400 step 1°F (if °F)
Range: –40 to +200 step 1°C (if °C)
–40 to +400 step 1°F (if °F)
Range: –40 to +200 step 1°C (if °C)
–40 to +400 step 1°F (if °F)
Range: 0 to 9999 step 1
DESIGNATES SETPOINTS THAT
ARE ONLY VISIBLE IF RTD
OPTION IS INSTALLED
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL