CHAPTER 4: PROGRAMMING
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
LRT Cold = Locked Rotor Time Cold, is defined as the locked rotor time when the
motor has been stopped for a time sufficient for the motor temperature to reach
ambient.
LRT Hot and LRT Cold are usually determined from the motor specifications. If this
information is not known, enter a typical value of 85% for the
.
RATIO
The
HOT/COLD CURVE RATIO
when the average phase current is at or below the FLC setpoint. When the motor is
cold (motor temperature at ambient) the thermal capacity used will be 0%. When the
motor is hot (motor running at FLC for a time sufficient to reach a steady state
temperature) the thermal capacity used will be calculated as 100% –
CURVE RATIO
, or 100 – 85 = 15% using the example value given above. In between
these two extremes there is a linear relationship; the 239 thermal model covers the
entire range of motor temperatures: cold—cool—warm—hot. The steady state value of
thermal capacity used for any phase current level can be calculated as:
Thermal Capacity Used
For example, if LRT Hot = 7.0 s, LRT Cold = 10.0 s, FLC = 100 A, and the actual motor
current is 80 A, then the steady state thermal capacity value will be:
Thermal Capacity Used
DISABLE STARTS: In some applications start protection may not be required.
Therefore, by setting this setpoint to
defeated. If the setpoint is set to
overload curves will be employed to protect the connected load.
This setpoint can also be used in conjunction with a switch input. If the
STARTS
setpoint is programmed to
described on page 46 is assigned to
defeated if the respective switch input is closed. The
programmed to
for the feature to work via the switch inputs.
YES
setpoint is used by the 239 to thermally model the motor
Actual Current
----------------------------------- -
×
(
100% HOT/COLD CURVE RATIO
=
FLC Setpoint
Actual Current
----------------------------------- -
×
(
100% HOT/COLD CURVE RATIO
=
FLC Setpoint
80
7.0
-------- -
×
100%
--------- -
×
100%
=
100
10.0
20%
=
, the start protection on the 239 can be
YES
, the 239 will go directly into run condition and
YES
YES
and
OPTION SWITCH 1-2 FUNCTION
, the 239 start protection will be
DISABLE STARTS
DISABLE STARTS
HOT/COLD CURVE
HOT/COLD
)
)
DISABLE
setpoint
setpoint must be
4–23