GE 239 Instruction Manual page 64

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

4–28
Courtesy of NationalSwitchgear.com
SEE PREVIOUS PAGE
SEE PREVIOUS PAGE
MESSAGE ▲
MESSAGE ▼
MESSAGE ▲
MESSAGE ▼
MESSAGE ▲
MESSAGE ▼
MESSAGE ▲
MESSAGE ▼
SEE NEXT PAGE
SEE NEXT PAGE
| MECHANICAL JAM
|
MECHANICAL JAM
FUNCTION: OFF
MECHANICAL JAM
PICKUP 2.0 x FLC
MECHANICAL JAM
DELAY: 2 s
INHIBIT ON START
FOR: UNLIMITED s
| UNDERCURRENT
|
UNDERCURRENT
FUNCTION: OFF
UNDERCURRENT
PICKUP 50% FLC
UNDERCURRENT
DELAY: 2 s
| UNBALANCE
|
PHASE UNBALANCE
TRIP: ON
PHASE UNBALANCE
TRIP PICKUP 20 %
PHASE UNBALANCE
DELAY: 2 s
PHASE UNBALANCE
ALARM: ON
PHASE UNBALANCE
ALARM PICKUP 5 %
| HOT MOTOR
|
THERMAL CAPACITY
USED ALARM OFF %
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL
CHAPTER 4: PROGRAMMING
Range: OFF, TRIP, ALARM,
AUXILIARY, TRIP&AUX
Range: 0.1 to 10.0
Step 0.1 x FLC
Range: 0 to 250; Step: 1 s.
Range: 0 to 6000, UNLIMITED
Step: 1 s
Range: OFF, ALARM, AUXILIARY,
TRIP, ALARM & AUX, TRIP & AUX
Range: 5 to 100; Step: 1%
Range: 0 to 250; Step: 1 s.
Range: ON, OFF
Range: 5 to 100; Step: 1%
Range: 0 to 60; Step: 1 s
Range: ON, OFF
Range: 5 to 100
Step: 1%
Range: 1 to 100; Step: 1%