3.4.7 Preparing field current cable C, connection to signal converter

DANGER!
A non-shielded three-wire copper cable is sufficient for the field current cable. If you
nevertheless use shielded cables, the shield must NOT
converter.
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
• Field current cable C is not part of the scope of delivery.
• Bending radius: ≥ 50 mm / 2"
Required materials:
• Shielded 3-wire copper cable with suitable heat-shrinkable tubing
• DIN 46 228 wire end ferrules: size according to the cable being used
Length and cross-section of field current cable C
1 Cu = copper cross-section
34-VF-25-53 iss.3 GLO Aug 10 US
Length
[m]
0...150
150...300
300...600
ELECTRICAL CONNECTIONS
NOT be connected in the housing of the signal
NOT
NOT
[ft]
[mm
0...492
492...984
984...1968
www.honeywell.com/ps
Cross-section A
(Cu)
F
2
]
3 x 0.75 Cu
1
3 x 1.50 Cu
1
3 x 2.50 Cu
1
3
[AWG]
3 x 18
3 x 14
3 x 12
27