3.4 Preparing the signal and field current cables

INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
The electrical connection of the outer shield is different for the various housing variants. Please
observe the corresponding instructions.

3.4.1 Signal cable A (type DS 300), construction

• Signal cable A is a double-shielded cable for signal transmission between the measuring
sensor and signal converter.
• Bending radius: ≥ 50 mm / 2"
Figure 3-1: Construction of signal cable A
1 Stranded drain wire (1) for the inner shield (10), 1.0 mm
2 Insulated wire (2), 0.5 mm
3 Insulated wire (3), 0.5 mm
4 Outer sheath
5 Insulation layers
6 Stranded drain wire (6) for the outer shield (60)
34-VF-25-53 iss.3 GLO Aug 10 US
2
Cu / AWG 20
2
Cu / AWG 20
www.honeywell.com/ps
ELECTRICAL CONNECTIONS
2
Cu / AWG 17 (not insulated, bare)
3