Power and Ground Wiring
The rated current of the equipment and associated voltage drop should be taken into
consideration when selecting wire gauge. The following example is based on an install
with a 28VDC power system, 1.5-amp equipment load and a total of 50 feet of wire
between the circuit breaker, monitor and ground.
Example: 22awg wire has 16.2 Ohms per 1000 feet, this equates to .81 Ohms for 50 feet.
1.5 Amp of current on .81 Ohms will drop 1.22 Volts.
Also, use short heavy gauge wire and a clean tight connection for ground.
It is the installer's responsibility to understand the product's requirements to install the
product in compliance with industry standards and safety.

Operation Instructions

The FD102CV-LP-S is continuously on but can be de-energized by removing power from
the entertainment system. No pilot or aircrew action is necessary during flight or ground
operation.
Passengers can change the video output from the FD102CV-LP-S using the video source
select switch on the included IR remote.
The IR LED, located on the top of the monitor, must be visible to the remote for wireless
operation.
© 2017 FDS Avionics Corp.
All Rights Reserved.
Document Number:
MAN – FD102CV-LP-S
Resistance of Wire Type M22759/16-**
(** = Gauge)
Gauge (AWG)
24
22
20
16
12
10
8
Rev:
B
OHMS/1000'
26.20
16.20
9.88
4.81
2.02
1.26
.701