18.9 Gas Conversion Setting:
Read the notes at the head of this section before commencing any work on
the appliance.
Insert a combustion analyser into the socket on the fl ue adapter.
Check the Potentiometer setting R31.
In order to set the appliance in service Mode turn the two control knob 2 Figure 18 to
minimum and switch the control knob 3 from OFF to On (Heating Mode) three times each
within a two second interval. A wrench symbol will be displayed in the LCD window and
the boiler will ignite at minimum rate.
In this mode of operation the gas rate will be controlled by the CH control for 15min,
after which time normal operation will take over and the wrench symbol will disappear.
With the CH control knob at minimum gas rate using a 4mm allen key adjust
the gas valve to give a CO
the CO
value, anti-clockwise: decrease CO
2
Please check CO
NOTE ALL GAS RATIOS MUST BE LESS THAN 0.004.
35
R 31 potentionmeter adjustment (clockwise)
SARGON 24
2 o'clock
value due to Technical Data table. (section 2) Clockwise: increase
2
values for maximum gas rate if required.
2
Figure 42
G20
SARGON 30 / 35
10 o'clock
value.
2