User Input Wiring - red lion PAX Product Manual

1/8 din analog input panel meters
Hide thumbs Also See for PAX:
Table of Contents

Advertisement

4.3 USER INPUT WIRING

Before connecting the wires, the User Input Logic Jumper should be verified for proper position. If not using User
Inputs, then skip this section. Only the appropriate User Input terminal has to be wired.
Sinking Logic
}
Terminal 8-10:
Connect external switching device between
Terminal 7:
appropriate User Input terminal and User Comm.
In this logic, the user inputs of the
meter are internally pulled up to +5 V
with 22 K resistance. The input is active
when it is pulled low (<0 .9 V).
PAXH ONLY
Sinking Logic
}
Terminals 9-11
Connect external
switching device between
Terminal 8
appropriate User Input
terminal and User Comm.
In this logic, the user inputs of the
meter are internally pulled up to +5 V
with 22 K resistance. The input is
active when it is pulled low (<0 .9 V).
4.4 SETPOINT (ALARMS) WIRING
4.5 SERIAL COMMUNICATION WIRING
4.6 ANALOG OUTPUT WIRING
5.0 r
evieWing THe
Display
Readout
Legends*
KEY
DISPLAY MODE OPERATION
DSP
Index display through max/min/total/input readouts
PAR
Access parameter list
F1
Function key 1; hold for 3 seconds for Second Function 1**
F2
Function key 2; hold for 3 seconds for Second Function 2**
RST
Reset (Function key)**
* Display Readout Legends may be locked out in Factory Settings.
** Factory setting for the F1, F2, and RST keys is NO mode.
7
8
9
10
8
9
10
11
See appropriate option card bulletin for details.
f
rOnT
8. 8 . 8 . 8 . 8
MA
X
MI
N
T
T O
S P
S 2
1
P
PAR
F1
DSP
Sourcing Logic
Terminal 8-10: + VDC thru external switching device
Terminal 7: -VDC thru external switching device
In this logic, the user inputs of the meter are
internally pulled down to 0 V with 22 K
resistance. The input is active when a voltage
greater than 3.6 VDC is applied.
Sourcing Logic
Terminals 9-11:
+ VDC through external switching device
Terminal 8:
-VDC through external switching device
In this logic, the user inputs of the meter are
internally pulled down with 22 K resistance.
The input is active when a voltage greater
than 3.6 VDC is applied.
b
UTTOns and
A
S
3
S
P
P4
F2
RST
PROGRAMMING MODE OPERATION
Quit programming and return to display mode
Store selected parameter and index to next parameter
Increment selected parameter value
Decrement selected parameter value
Hold with F1
, F2
to scroll value by x1000
15
7
8
9
-
+
V
(30V max.)
SUPPLY
8
9
10
-
+
V
SUPPLY
(30V max.)
d
isplay
Optional Custom
Units Overlay
Setpoint Alarm
Annunciators
10
11