8.2 Resetting Totalizer 1
1.
Press UP key to scroll to "total 1" display.
2.
Press and hold the RIGHT arrow key until the display shows "rst tot1".
The totalizer will À ash for 8 seconds and then it will automatically reset to 00000000.
Press the ENTER key while the display is À ashing to reset immediately.
While the total value is À ashing, you can cancel the reset by pressing UP and DOWN keys together.
Totalizer #1 will be displayed for 5 minutes after the reset, then the standard totalizer selection will return.
Press the UP or DOWN key to scroll back to the standard display immediately.
External Reset: See section 4: Wiring for information on resetting Totalizer #1 remotely from up to 30 meters distance. NOTE: When
Total #1 is reset from an external switch, the display will not show totalizer #1 unless it has been set as the standard totalizer.
1
Signet Total Flow
ENTER
8.3 Resetting Totalizer 2
Totalizer #2 can be reset ONLY by entering the security code.
1.
Press ENTER key for 2 seconds. (Display shows security key symbol and 0-0-0-0)
2.
Set the security code in the À ashing display and then press the ENTER key.
3.
Press UP key one time. (Display shows "tot2 reset")
4.
Press RIGHT ARROW key. The totalizer value will begin À ashing.
The totalizer will automatically reset to 00000000 in 8 seconds.
While the display is À ashing, you can cancel the reset by pressing UP and DOWN keys together.
5.
Press UP and DOWN keys together to return to normal operation.
1
4
8.4 Saving Totalizer Values
To conserve battery life, totalizer values are stored in the memory every 12 hours. If both batteries are removed from the unit, the
totalizers retain the last saved values, so the unit may lose several hours of data.
To prevent this loss, enter the security code, then enter any menu item and store the setting.
Whenever the 8150 stores a setting, it also stores all current totalizer data:
1.
Enter the security code.
2.
Press the UP key to scroll to the last item in the menu (DEFAULT TOTALIZER)
3.
Press the RIGHT key to enter the edit mode (À ashing display mode)
4.
Press the ENTER key to retain the current settings.
5.
Press the UP and DOWN keys simultaneously to initiate the "Storing" function.
The batteries can now be removed and replaced without losing any totals.
8
2
Signet Total Flow
Signet Total Flow
ENTER
2 s
2
ENTER
2 s
Enter security code
Signet Total Flow
8 s
Signet Total Flow
ENTER
8 s
5 m
3
5
Signet Total Flow
ENTER
8150 Flow Totalizer