‡ SIGNET 8550-1 Flow Transmitter
3-8550.090-1
CAUTION!
Remove power to unit before wiring
input and output connections.
Follow instructions carefully to avoid
personal injury.
1. Installation
ProcessPro transmitters are available in two styles: panel mount and field mount. The panel mount is supplied with the necessary
hardware to install the transmitter. This manual includes complete panel mounting instructions.
Field mounting requires one of two separate mounting kits. The 3-8051 integral kit joins the sensor and instrument together into a
single package. The 3-8050 Universal kit enables the transmitter to be installed virtually anywhere.
Detailed instructions for integral mounting or other field installation options are included with the 3-8051 Integral kit or the 3-8050
Universal kit.
1.1 Panel Installation
1.
The panel mount transmitter is designed for installation using a 1/4 DIN Punch. For manual panel cutout, an adhesive
template is provided as an installation guide. Recommended clearance on all sides between instruments is 1 inch.
2.
Place gasket on instrument, and install in panel.
3.
Slide mounting bracket over back of instrument until quick-clips snap into latches on side of instrument.
4.
To remove, secure instrument temporarily with tape from front or grip from rear of instrument. DO NOT RELEASE.
Press quick-clips outward and remove.
96 mm
(3.8 in.)
96 mm
(3.8 in.)
FRONT VIEW
Field Mount &
Panel Mount

2 . Specifications

General
Compatibility: +GF+ SIGNET Flow Sensors (w/freq out)
Accuracy: ±0.5 Hz
Enclosure:
Rating:
NEMA 4X/IP65 front
Case:
PBT
Panel case gasket:
Neoprene
Window:
Polyurethane coated polycarbonate
Keypad:
Sealed 4-key silicone rubber
Weight:
Approx. 325g (12 oz.)
Display:
Alphanumeric 2 x 16 LCD
Update rate: 1 second
Contrast: User selected, 5 levels
Electrical
Power: 12 to 24 VDC ±10%, regulated, 61 mA max current
Sensor Input:
Range: 0.5 to 1500 Hz
Sensor power: 2-wire: 1.5 mA @ 5 VDC ± 1%
3 or 4 wire: 20 mA @ 5 VDC ± 1%
Optically isolated from current loop
Short circuit protected
Current output:
4 to 20 mA, isolated, fully adjustable and reversible
‡ SIGNET 8550-1 Flow Transmitter
C-3/01 English
96 mm
(3.8 in.)
102 mm
(4.0 in.)
SIDE VIEW
Field Mount
Contents
1. Installation
2. Specifications
3. Electrical Connections
4. Menu Functions
Optional
92 mm
Rear
(3.6 in.)
Cover
56 mm
41 mm
(2.2 in.)
)
(1.6 in.
97 mm
(3.8 in.)
SIDE VIEW
Panel Mount
Max loop impedance:
Update rate: 100 ms
Accuracy: ±0.03 mA
Open-collector output, optically isolated:
50 mA max. sink, 30 VDC maximum pull-up voltage.
Programmable for:
High or Low setpoint with adjustable hysteresis
Pulse operation (max rate: 300 pulses/min).
Environmental
Operating temperature: -10 to 70°C (14 to 158°F)
Storage temperature:
Relative humidity:
Maximum altitude:
Insulation category:
Pollution degree:
Standards and Approvals
CSA, CE, UL listed
Immunity:
EN50082-2
Emissions:
EN55011
Safety:
EN61010
Manufactured under ISO 9001 and ISO 14001
ENGLISH
Flow
Flow 6.25 GPM
Total 1234567.8>
panel
gasket
terminals
latch
Panel Mount
Installation Detail
quick-clips
50 Ω max. @ 12 V
325 Ω max. @ 18 V
600 Ω max. @ 24V
-15 to 80°C (5 to 176°F)
0 to 95%, non-condensing
2000 m (6562 ft)
II
2
page 1 of 8
ENTER
mounting
bracket

Advertisement

Table of Contents
loading

Summary of Contents for Signet 8550-1

  • Page 1: Specifications

    2 . Specifications 50 Ω max. @ 12 V • Max loop impedance: General 325 Ω max. @ 18 V Compatibility: +GF+ SIGNET Flow Sensors (w/freq out) 600 Ω max. @ 24V Accuracy: ±0.5 Hz • Update rate: 100 ms Enclosure: Accuracy: ±0.03 mA...
  • Page 2: Electrical Connections

    Power + (BLACK) Terminals 1 and 2: AUXILIARY power Internal open-collector Used only if the flow sensor requires output circuit more than 1.5 mA current. For Signet 15Ω sensors this is limited to the following Output -- products: • 2000 •...
  • Page 3 4-20 mA in Power + AUXILIARY power is used only if the flow sensor requires more * See AUX POWER Note than 1.5 mA current. For Signet sensors this is limited to the following products: • 2000 • 2507 • 2530 •...
  • Page 4: View Menu

    Monitor the Permanent Totalizer value. Gallons Loop Output: Monitor the 4-20 mA Loop output. 12.00 mA Last CAL: Monitor date for scheduled maintenance or date of last calibration. (See description in Calibrate Menu.) 06-30-01 ‡ SIGNET 8550-1 Flow Transmitter page 4 of 8...
  • Page 5 This will recall the Output Setpnt: Saving last saved value of the item being edited and return you to Step 3. Output Setpnt: 19.00 GPM > ‡ SIGNET 8550-1 Flow Transmitter page 5 of 8...
  • Page 6: Calibrate Menu

    (2, 4, 6, 8 . . . 254 maximum) to scale output frequency. Divide by 1 > Use this “note pad” to record important dates, such as annual recertification or scheduled Last CAL: maintenance. 6-30-01 ‡ SIGNET 8550-1 Flow Transmitter page 6 of 8...
  • Page 7: Options Menu

    Press UP or DOWN keys to manually order any output current value from 3.6 mA to 21.00 mA to test current loop output. > Test Output: Press UP or DOWN keys to manually toggle the state of open collector output. > ‡ SIGNET 8550-1 Flow Transmitter page 7 of 8...
  • Page 8: Troubleshooting

    • Replace transmitter ‡ SIGNET Signet Scientific Company, 3401 Aerojet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057 For Worldwide Sales and Service, visit our website: gfsignet.com • Or call (in the U.S.): (800) 854-4090 GEORGE FISCHER ‡...