Signet 8450-2 Pressure Transmitter
*3-8450.090-2*
3-8450.090-2
Rev. J 11/11
CAUTION!
•
Remove power to unit before wiring input
and output connections.
•
Follow instructions carefully to avoid
personal injury.
1. Installation
ProcessPro transmitters are available in two styles: panel mount and fi eld mount. The panel mount is supplied with the necessary
hardware to install the transmitter. This manual includes complete panel mounting instructions.
Field mounting requires one of two separate mounting kits. The 3-8052 integral kit joins the sensor and instrument together into a single
package. The 3-8050 Universal kit enables the transmitter to be installed virtually anywhere.
Detailed instructions for integral mounting or other fi eld installation options are included with the 3-8052 Integral kit or the 3-8050
Universal kit.
1.1 Panel Installation
1. The panel mount transmitter is designed for installation using a 1/4 DIN Punch. For manual panel cutout, an adhesive template is
provided as an installation guide. Recommended clearance on all sides between instruments is 1 inch.
2. Place gasket on instrument, and install in panel.
3. Slide mounting bracket over back of instrument until quick-clips snap into latches on side of instrument.
4. To remove, secure instrument temporarily with tape from front or grip from rear of instrument. DO NOT RELEASE.
Press quick-clips outward and remove.
96 mm
(3.8 in.)
96 mm
(3.8 in.)
FRONT VIEW
Field Mount &
Panel Mount
2. Specifi cations
General
Compatibility: Signet 2450 Pressure Sensor
Accuracy: ±1% of full scale
Repeatability: ±0.5% of full scale
Enclosure:
•
Case:
PBT
•
Panel case gasket: Neoprene
•
Window:
Polyurethane coated polycarbonate
•
Keypad:
Sealed 4-key silicone rubber
•
Weight:
Approx. 325 g (12 oz.)
Display:
•
Alphanumeric
2 x 16 LCD
•
Update rate:
1 second
•
Contrast:
User selected, 5 levels
Electrical
Sensor Input:
•
Range:
0-250 psig, 0-17 bar, 0-1700 kPa
Current output:
•
4 to 20 mA, isolated, fully adjustable and reversible
•
Power: 12 to 24 VDC ±10%, regulated, 21 mA max current
•
Max loop impedance:
English
8052
42 mm
65 mm
(1.7 in.)
(2.5 in.)
107 mm (4.2 in.)
SIDE VIEW
Field Mount
50 Ω max. @ 12 V
325 Ω max. @ 18 V
600 Ω max. @ 24 V
Contents
1. Installation
2. Specifi cations
3. Electrical Connections
4. Menu Functions
Optional
96 mm
Rear
(3.8 in.)
Cover
56 mm
41 mm
(2.2 in.)
)
(1.6 in.
97 mm
(3.8 in.)
SIDE VIEW
Panel Mount
•
Update rate:
•
Accuracy:
Relay outputs (2 sets mechanical SPDT contacts):
•
Maximum voltage rating: 5 A @ 30 VDC, or 5 A @ 250 VAC
resistive load
•
Hi or Lo programmable with adjustable hysteresis
•
Pulse programmable (maximum 400 pulses/minute)
•
Hysteresis:
Environmental
•
Operating temperature:
•
Storage temperature:
•
Relative humidity:
•
Maximum altitude:
•
Insulation category:
•
Rating:
Standards and Approvals
•
CE, UL listed
•
Immunity:
•
Emissions:
•
Manufactured under ISO 9001 for Quality and
ISO 14001 for Environmental Management
China RoHS (Go to www.gfsignet.com for details)
panel
gasket
92 mm
(3.6 in.)
latch
Panel Mount
Installation Detail
100 ms
±0.03 mA
User adjustable
-10 to 70 °C (14 to 158 °F)
-15 to 80 °C (5 to 176 °F)
0 to 95%, non-condensing
2000 m (6562 ft)
II
NEMA 4X/IP65 front
EN50082-2
EN55011 Class B
English
Pressure Cal:
0.0
psi >
Signet Pressure
Transmitter
Relay 1
Relay 2
ENTER
mounting
bracket
terminals
quick-clips