6. Operation

The 8150-1 display shows the À ow rate in large numerals and
a totalizer value in smaller numerals. Any one of three different
totalizers can be selected as the standard display (See section 8
for detailed information on the totalizers).
Press the UP or DOWN keys to scroll through all three totalizer
values during normal operation.
6.1 No Flow and ELAPSED TIME Display
If the À ow stops, the Flow Rate displays the number of hours
since À ow was last detected. This display will alternate with the
normal Totalized Value and standard "no FLo" display every ¿ ve
seconds.
Any movement of the rotor in the pipe will reset the ELAPSED
TIME display.
6.2 Standard Menu Settings
Totalizers are shipped from the factory with these standard settings:
Function:
Factory set:
AUTO CALIBRATION
FLOW K-FACTOR
60
TOTAL K-FACTOR
1
TIMEBASE
Minutes
DECIMAL
XXX.X
SPEED
30 s
SENSITIVITY
6
SECURITY CODE
0-0-0-0
DEFAULT TOTALIZER
Permanent
TOTALIZER #2 RESET
8150 Flow Totalizer
Illustrated: No À ow for 3 hours
Description:
No setting; See section 9 for detailed information.
Number of sensor pulses per volumetric unit; Refer to sensor manual.
Set the number of volumetric units per totalizer count; see section 11.
Select À ow rate in seconds, minutes, hours or days. Section 12.
Set the maximum decimal resolution. Section 13.
Zero to 120 seconds averaging stabilizes readings in erratic À ow conditions. Section 14.
Momentarily overrides SPEED when À ow rate changes signi¿ cantly. Section 15.
Set a private code to prevent tampering. Section 7.
Select from three totalizer options. Section 8.
Reset Totalizer #2 after entering the security code. Section 8.3.
Signet Total Flow
Signet Total Flow
5 sec.
5