Mitsubishi Electric FR-F720-55K Instruction Manual page 76

Fr-a7nf series inverter plug-in option fl remote communication function
Hide thumbs Also See for FR-F720-55K:
Table of Contents

Advertisement

MESSAGE TRANSMISSON
Inverter monitor value of each monitor is as in the table below. Refer to the inverter manual for details of
each monitor. (When accessing a message, the access size should be 2 byte (1 word).)
Code
Description
number
H10000190 Output frequency
H10000192 Output current
H10000194 Output voltage
H10000198 Set frequency
H1000019A Running speed
H1000019C Motor torque
H1000019E Converter output voltage
H100001A0 Regenerative brake duty
Electronic thermal relay
H100001A2
function load factor
H100001A4 Output current peak value
H100001A6 Converter output voltage peak
value
H100001A8 Input power
H100001AA Output power
H100001AC Input terminal status
H100001AE Output terminal status
H100001B0 Load meter
H100001B2 Motor excitation current
H100001B4 Position pulse
H100001B6 Cumulative energization time
H100001BA Orientation status
H100001BC Actual operation time
70
Unit
0.01Hz
*11
0.01A/0.1A
0.1V
0.01Hz
1
0.1%
*2
0.1V
0.1%
0.1%
0.01A/0.1A
0.1V
0.01kW/
0.1kW
0.01kW/
0.1kW
*6
*7
0.1%
0.01A/0.1A
*2
*2, *5
1h
*2, *5
1h
Code
number
H100001BE Motor load factor
H100001C0 Cumulative power
*1
H100001CE Torque command
H100001D0 Torque current command
H100001D2 Motor output
H100001D4 Feedback pulse
Motor temperature monitor
H100001EA
output
H100001F2 Power saving effect
*1
H100001F4 Cumulative saving power
H100001F6 PID set point
*1
H100001F8 PID measured value
*1
H100001FA PID deviation
H10000202 Option input terminal status
H10000204 Option input terminal status 2
H10000206 Option output terminal status
*1
H10000214 PID measured value 2
H10000228 Cumulative power (lower 16 bits)
H1000022A Cumulative power (upper 16 bits)
H1000022C Cumulative power (lower 16 bits)
Description
*2
*2
*2
*2, *5
*2
*2, *8
*2, *9
*2, *10
*4
*3
*3
*3
Unit
0.1%
1kWh
0.1%
0.1%
0.01kW/
0.1kW
*1
°
1
C
Variable
according to
parameters
Variable
according to
parameters
0.1%
0.1%
0.1%
0.1%
1kWh
1kWh
0.01kW/
0.1kW
*1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents