Carrier 42/38SHDS050 Installation Manual page 19

Slim ducted air conditioner
Table of Contents

Advertisement

5. Clamp flare form on the end of the pipe.
The end of the pipe must extend beyond
the flare form.
Flare form
Fig. 7.5
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise
until the pipe is fully flared. Flare the pipe in
accordance with the dimensions shown in
table 7.5.
Table 7.5: PIPING EXTENSION BEYOND FLARE FORM
Pipe
Tightening
Flare dimension (A)
torque
gauge
14.2-17.2 N.m
Ø 6.4
(144-176 kgf.cm)
32.7-39.9 N.m
Ø 9.5
12.4/0.48
(333-407 kgf.cm)
49.5-60.3 N.m
Ø 12.7
15.4/0.6
(504-616 kgf.cm)
61.8-75.4 N.m
Ø 15.9
18.6/0.7
(630-770 kgf.cm)
97.2-118.6 N.m
Ø 19.1
(990-1210 kgf.cm)
22.9/0.9
109.5-133.7 N.m
Ø 22
(1117-1364 kgf.cm)
27/1.06
8. Remove the flaring tool and flare form, then
inspect the end of the pipe for cracks and
even flaring.
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first,
then connect it to the outdoor unit. You should
first connect the low-pressure pipe, then the high-
pressure pipe.
1. When connecting the flare nuts, apply a thin coat
of refrigeration oil to the flared ends of the pipes.
2. Align the center of the two pipes that you
will connect.
Indoor unit tubing
Fig. 7.7
3. Tighten the flare nut as tightly as possible by hand.
4. Using a spanner, grip the nut on the unit tubing.
5. While firmly gripping the nut, use a torque
wrench to tighten the flare nut according to
the torque values in table 7.5.
Pipe
Flare shape
(Unit: mm/Inch)
Min.
Max .
90 ° ± 4
8.3/0.3
8.3/0.3
A
12.4/0.48
15.8/0.6
19/0.74
Fig. 7.6
23.3/0.91
27.3/1.07
Pipe
Flare nut
NOTE: Use both a spanner and a torque wrench
when connecting or disconnecting pipes to/from
the unit.
CAUTION
Ensure to wrap insulation around the piping.
Direct contact with the bare piping may result
in burns or frostbite.
Make sure the pipe is properly connected.
Over tightening may damage the bell mouth
and under tightening may lead to leakage.
NOTE ON MINIMUM BEND RADIUS
Carefully bend the tubing in the middle according
to the diagram below. DO NOT bend the tubing
more than 90° or more than 3 times.
Bend the pipe with thumb
R0.4~0. 8
6. After connecting the copper pipes to the
indoor unit, wrap the power cable, signal
cable and the piping together with binding
tape.
NOTE: DO NOT intertwine signal cable with
other wires. While bundling these items
together, do not intertwine or cross the signal
cable with any other wiring.
7. Thread this pipeline through the wall and
connect it to the outdoor unit.
8. Insulate all the piping, including the valves
of the outdoor unit.
9. Open the stop valves of the outdoor unit
to start the flow of the refrigerant
between the indoor and outdoor unit.
CAUTION
Check to make sure there is no refrigerant leak
after completing the installation work. If there is
a refrigerant leak, ventilate the area immediately
and evacuate the system (refer to the Air
Evacuation section of this manual).
min-radius 10cm (3.9")
Fig. 7.8
Fig. 7.9
Page 19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

42/38shds09042/38shds07042/38shds100

Table of Contents